background image

Venting

When installing the venting system, make sure to 
follow all local codes or, in the absence of local 
codes, CSA B149.1 in Canada and/or the National 
Fuel Gas Code, ANSI Z223.1 in the United 
States. Never operate the water heater unless 
it is properly ventilated to the outdoors and has 
adequate air supply for proper operation. Failure 
to properly install the venting system could result 
in property damage, personal injury, or death.

Draft Hood installation
The water heater must be vented using the draft 
hood provided by the manufacturer. Before installing 
the draft hood, check to make sure that the flue baffle 
has been installed in the flue tube. If the flue baffle 
is missing, immediately contact the dealer where 
the water heater was purchased. Never operate the 
water heater without the flue baffle installed. 
To install the draft hood, place it over the flue opening 
on the top of the water heater. When installing the 
draft hood do not alter it in any way. 

UG30 and UG40 Models

Line up the holes in the draft hood’s legs with those of 
the water heater’s top and secure the draft hood using 
the two (2) sheet metal screws provided (see Figure 7a). 

UG50 and UG60 Models

Line up the legs of the draft hood with the holes with 
those of the water heater’s top and snap into position. 
Then insert the two (2) sheet metal screws provided 
into the same holes to secure legs down into place 
(see Figure 7b).

Venting System
The venting system must be attached to the draft 
hood to connect the water heater to the gas vent 
or chimney. The vent pipe connecting to the water 
heater must be of the same size as the draft hood. 
It is highly recommended to install this water heater 
on a separate venting system from other appliances. 
In some installations, proper venting may require the 
use of a larger diameter vent pipe and/or combined 
venting with other appliances. Consult the vent tables 
in the CSA B149.1 in Canada and/or the National 
Fuel Gas Code, ANSI Z223.1 in the United States to 
correctly size the vent pipe.
When connecting the vent pipe to the water heater 
the following instructions must be followed:
•  Install the vent pipe in such a way as to avoid any 

unnecessary bends that could create resistance to 
the flow of combustion gases.

•  The horizontal length of the vent pipe must not 

exceed 75% of the vertical vent height, in no case 
shall it exceed twenty (20) feet (6.1 m) horizontally.

•  All horizontal runs must have a minimum rise of  

1/4 inch per foot (21 mm/m) of run (See Figure 8).

•  All joints must be securely fastened with sheet 

metal screws or other approved means.

•  All single wall vent piping must maintain a minimum 

of six (6) inches (15.2 cm) of clearance from 
combustible materials.

• Venting systems made with single wall piping 

cannot pass through any attic, inside wall, 
crawlspace, confined space, or any floor.

•  The vent piping must be accessible for inspection, 

cleaning, and replacement.

When the installation is complete, visually inspect 
the venting system to make sure that all joints are 
properly connected and all instructions have been 
followed. Failure to properly install the venting  
system could result in property damage, personal 
injury, or death.

Water Piping
Refer to Figure 8 for a typical installation. Use of 
this layout should provide a trouble-free installation 
for the life of the water heater. Before making the  
plumbing connections, locate the COLD water inlet 
and the HOT water outlet. These fittings are both 
3/4” NPT male thread. Make sure that the dip tube is 
installed in the cold water inlet. Install a shut-off valve 
close to the water heater in the cold water line. It is 
recommended that unions be installed in the cold and 
hot water lines so that the water heater can be easily 
disconnected, if servicing is required.

7

INSTALLATION INSTRUCTIONS

Draft Hood

Figure 7a

Draft Hood

Figure 7b

Содержание UG30

Страница 1: ...n may result causing property damage personal injury or death DO NOT store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL...

Страница 2: ...eplacement Parts 16 Troubleshooting Guide 17 Warranty 19 FVIR technology equipped with flame arrestor This water heater is equipped with the new FVIR technology In the event that gasoline or other fla...

Страница 3: ...ol alerts you to potential hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER or WARNING Serious injury or death can occur...

Страница 4: ...structions to prevent damage to the building Under no circumstances is the manufacturer to be held liable for any water damage in connection with this water heater This water heater is approved for in...

Страница 5: ...ll appliances and shall communicate directly with one or more rooms of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space for all the appliances ins...

Страница 6: ...f the total input rating of all gas appliances in the confined space see Figure 6 Install above insulation Attic air inlet Outlet air to attic 1 sq in 4 000 Btuh Confined Space Inlet air duct 1 sq in...

Страница 7: ...pipe and or combined venting with other appliances Consult the vent tables in the CSA B149 1 in Canada and or the National Fuel Gas Code ANSI Z223 1 in the United States to correctly size the vent pi...

Страница 8: ...hydrostatic working pressure of the water heater 150 psi 1 035 kPa and a Btuh rating equal to or greater than the input rating as shown on the water heater rating plate It should never be plugged or...

Страница 9: ...etely full of water open hot water faucets to let the air out of the water heater and plumbing system Leave the faucets open until a constant flow of water is obtained 4 Check all of the plumbing conn...

Страница 10: ...e past treated with chemicals for cleaning or sealing the system 3 If this water heater is to be used for space heating make sure that all safety codes are respected Pay special attention to safety va...

Страница 11: ...hood been installed correctly L Is the vent piping made of an approved material and sized correctly L Has the venting been installed with 1 4 inch rise per foot 21 mm m of horizontal run L Has all th...

Страница 12: ...mmediately call a qualified service technician to inspect the water heater and to replace any part of the control system and any gas control which has been under water 1 STOP Read the safety informati...

Страница 13: ...Turn the temperature dial clockwise to decrease the temperature or counterclockwise to increase the temperature The reference mark on the temperature dial indicated by a large triangle represents 130...

Страница 14: ...connections to make sure they are not leaking Main Burner Pilot Every three 3 months check the main burner and pilot flame Remove the outer access door and look through the sight glass to examine the...

Страница 15: ...2 Depress slightly and turn the gas control knob clockwise to the OFF position 3 Close the gas supply manual shut off valve 4 Close the cold water supply manual shut off valve 5 Connect one end of a g...

Страница 16: ...tube 8 Baffle 9 Flue reducer 10 Draft hood 11 Anode 12 Dip tube 13 Temperature pressure relief valve 1 Manifold Spring on some models 2 Manifold 3 Inner Left Door 4 Access Door 5 Thermal High Limit S...

Страница 17: ...control The flame burns at the orifice Low gas pressure Check with gas utility company Defective gas control Replace with new gas control The pilot will not light or remain lit No gas Check with gas u...

Страница 18: ...Condensation Water drips from the relief valve Heater stacking Lower gas control setting Excessive water pressure Install a pressure reducing valve Thermal expansion in a closed water system Install...

Страница 19: ...10 To any damage caused by not having the unit installed adjacent to a free flowing drain or in a pan or basin connected to such free flowing drain 11 For all equipment operated at water temperatures...

Страница 20: ...cted to such free flowing drain 11 For all equipment operated at water temperatures exceeding the maximum operating setting of the thermostat and or the high limit control at a pressure exceeding the...

Отзывы: