(100) square inches (645.16 cm²). The first opening 
should be situated within six (6) inches (15.2 cm) of 
the top and the second opening within six (6) inches 
(15.2 cm) of the bottom of the confined space.

2) All Air From Outdoors:
  The confined space shall be provided with two (2 

permanent openings, the first opening within six (6) 
inches (15.2 cm) of the top and the second within 
six (6) inches (15.2 cm) from the bottom of the 
confined space. The openings shall communicate 
directly, or by ducts, with the outdoors or spaces 
(crawl or attic) that freely communicates with the 
outdoors.

  A) When communicating directly with the outdoors, 

each opening shall have a minimum free area of 
one (1) square inch per 4,000 Btuh (5.5 cm²/kW) of 
the total input rating of all gas appliances in the 
confined space (see Figure 4).

Confined Space

Permanent

Opening

--------------

1 square inch /

1,000 Btuh

(min.: 100 sq. in)

Outlet air to attic

1 sq. in / 4,000 Btuh

Attic air inlet

Install above

insulation

Confined Space

Inlet air from the

crawl space

1 sq. in / 4,000 Btuh

Open foundation vent

Install above

insulation

Attic air inlet

Outlet air to attic

1 sq. in / 4,000 Btuh

Confined Space

Inlet air duct

1 sq. in / 4,000 Btuh

12'' max.

Inlet

Outlet

Outdoor air duct

1 sq. in. / 2,000 Btuh

1 sq. in. / 2,000 Btuh

Confined Space

Alternate

air inlet

Entrée d'air

Alternative

1 po

2

 / 2 000 BTUH

1 po

2

 / 2 000 BTUH

Conduit d'air extérieur

Sortie

Entrée

12'' max.

Conduit d'entrée d'air

1 po

2

 / 4 000 BTUH

Évent de fondation

1 po

2

 / 4 000 BTUH 

Entrée d'air du

sous-sol

Espace Restreint

Installez au-dessus

de l'isolation

Entrée d'air

 du grenier

Sortie d'air

au grenier

1 po

2

 / 4 000 BTUH 

Ouverture

Permanente

--------------

1 pouce carré /

1 000 BTUH

(min. : 100 po

2

)

Espace Restreint

Entrée d'air

du grenier

Installez au-dessus

de l'isolation

Espace Restreint

Sortie d'air

au grenier

1 po

2

 / 4 000 BTUH

Espace Restreint

Gas vent to

outdoors

Évacuation de gaz

vers l'extérieur

Gas vent to

outdoors

Évacuation de gaz

vers l'extérieur

Gas vent to

outdoors

Évacuation de gaz

vers l'extérieur

Gas vent to

outdoors

Évacuation de gaz

vers l'extérieur

Figure 4

  B) When communicating with the outdoors through 

vertical ducts, each opening shall have a minimum 
free area of one (1) square inch per 4,000 Btuh 
(5.5 cm²/kW) of the total input rating of all gas 
appliances in the confined space (see Figure 5).

Confined Space

Permanent

Opening

--------------

1 square inch /

1,000 Btuh

(min.: 100 sq. in)

Outlet air to attic

1 sq. in / 4,000 Btuh

Attic air inlet

Install above

insulation

Confined Space

Inlet air from the

crawl space

1 sq. in / 4,000 Btuh

Open foundation vent

Install above

insulation

Attic air inlet

Outlet air to attic

1 sq. in / 4,000 Btuh

Confined Space

Inlet air duct

1 sq. in / 4,000 Btuh

12'' max.

Inlet

Outlet

Outdoor air duct

1 sq. in. / 2,000 Btuh

1 sq. in. / 2,000 Btuh

Confined Space

Alternate

air inlet

Entrée d'air

Alternative

1 po

2

 / 2 000 BTUH

1 po

2

 / 2 000 BTUH

Conduit d'air extérieur

Sortie

Entrée

12'' max.

Conduit d'entrée d'air

1 po

2

 / 4 000 BTUH

Évent de fondation

1 po

2

 / 4 000 BTUH 

Entrée d'air du

sous-sol

Espace Restreint

Installez au-dessus

de l'isolation

Entrée d'air

 du grenier

Sortie d'air

au grenier

1 po

2

 / 4 000 BTUH 

Ouverture

Permanente

--------------

1 pouce carré /

1 000 BTUH

(min. : 100 po

2

)

Espace Restreint

Entrée d'air

du grenier

Installez au-dessus

de l'isolation

Espace Restreint

Sortie d'air

au grenier

1 po

2

 / 4 000 BTUH

Espace Restreint

Gas vent to

outdoors

Évacuation de gaz

vers l'extérieur

Gas vent to

outdoors

Évacuation de gaz

vers l'extérieur

Gas vent to

outdoors

Évacuation de gaz

vers l'extérieur

Gas vent to

outdoors

Évacuation de gaz

vers l'extérieur

Figure 5

  C) When communicating with the outdoors through 

horizontal ducts, each opening shall have a minimum 
free area of one (1) square inch per 2,000 Btuh  
(11.0 cm²/kW) of the total input rating of all gas 
appliances in the confined space (see Figure 6).

Confined Space

Permanent

Opening

--------------

1 square inch /

1,000 Btuh

(min.: 100 sq. in)

Outlet air to attic

1 sq. in / 4,000 Btuh

Attic air inlet

Install above

insulation

Confined Space

Inlet air from the

crawl space

1 sq. in / 4,000 Btuh

Open foundation vent

Install above

insulation

Attic air inlet

Outlet air to attic

1 sq. in / 4,000 Btuh

Confined Space

Inlet air duct

1 sq. in / 4,000 Btuh

12'' max.

Inlet

Outlet

Outdoor air duct

1 sq. in. / 2,000 Btuh

1 sq. in. / 2,000 Btuh

Confined Space

Alternate

air inlet

Entrée d'air

Alternative

1 po

2

 / 2 000 BTUH

1 po

2

 / 2 000 BTUH

Conduit d'air extérieur

Sortie

Entrée

12'' max.

Conduit d'entrée d'air

1 po

2

 / 4 000 BTUH

Évent de fondation

1 po

2

 / 4 000 BTUH 

Entrée d'air du

sous-sol

Espace Restreint

Installez au-dessus

de l'isolation

Entrée d'air

 du grenier

Sortie d'air

au grenier

1 po

2

 / 4 000 BTUH 

Ouverture

Permanente

--------------

1 pouce carré /

1 000 BTUH

(min. : 100 po

2

)

Espace Restreint

Entrée d'air

du grenier

Installez au-dessus

de l'isolation

Espace Restreint

Sortie d'air

au grenier

1 po

2

 / 4 000 BTUH

Espace Restreint

Gas vent to

outdoors

Évacuation de gaz

vers l'extérieur

Gas vent to

outdoors

Évacuation de gaz

vers l'extérieur

Gas vent to

outdoors

Évacuation de gaz

vers l'extérieur

Gas vent to

outdoors

Évacuation de gaz

vers l'extérieur

Figure 6

When ducts are used, they shall be of the same 
cross-sectional area as the free area of the openings 
to which they connect. The minimum short side 
dimension of rectangular air ducts shall not be less 
than three (3) inches (7.62 cm).
Louvers and Grilles
In calculating free area for ventilation and combustion 
air supply openings, consideration must be given 
to the blocking effect of louvers, grilles, or screens 
protecting the openings. Screens must not be smaller 
than 1/4 inch (6.4 mm) mesh. If the free area through 
a particular design of louver or grille is known, it 
should be used in calculating the size of opening 
required to provide the free area specified. If the 
design and free area is unknown, it may be assumed 
that wood louvers and grilles will allow 20-25% free 
area and metal louvers and grilles will allow 60-75% 
free area. Louvers and grilles must be installed in the 
open position or interconnected with the water heater 
so that they are opened automatically during water 
heater operation.
Corrosive Atmospheres 

If this water heater will be installed in a beauty shop, 

barber shop, photo processing lab, dry cleaning 

establishment, a building with an indoor pool, or 

near a chemical storage area, it is imperative that 

the combustion and ventilation air be drawn from 

outside these areas. These particular environments 

contain products such as aerosol sprays, detergents, 

bleaches, cleaning solvents, refrigerants, and other 

volatile compounds that, in addition to being highly 

flammable, become highly corrosive acid compounds 

when burned. Exposure to such compounds can be 

hazardous and lead to premature product failure. 

Should the water heater fail due to exposure to 

such a corrosive atmosphere, the warranty is void.

6

INSTALLATION INSTRUCTIONS

Содержание UG30

Страница 1: ...n may result causing property damage personal injury or death DO NOT store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL...

Страница 2: ...eplacement Parts 16 Troubleshooting Guide 17 Warranty 19 FVIR technology equipped with flame arrestor This water heater is equipped with the new FVIR technology In the event that gasoline or other fla...

Страница 3: ...ol alerts you to potential hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER or WARNING Serious injury or death can occur...

Страница 4: ...structions to prevent damage to the building Under no circumstances is the manufacturer to be held liable for any water damage in connection with this water heater This water heater is approved for in...

Страница 5: ...ll appliances and shall communicate directly with one or more rooms of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space for all the appliances ins...

Страница 6: ...f the total input rating of all gas appliances in the confined space see Figure 6 Install above insulation Attic air inlet Outlet air to attic 1 sq in 4 000 Btuh Confined Space Inlet air duct 1 sq in...

Страница 7: ...pipe and or combined venting with other appliances Consult the vent tables in the CSA B149 1 in Canada and or the National Fuel Gas Code ANSI Z223 1 in the United States to correctly size the vent pi...

Страница 8: ...hydrostatic working pressure of the water heater 150 psi 1 035 kPa and a Btuh rating equal to or greater than the input rating as shown on the water heater rating plate It should never be plugged or...

Страница 9: ...etely full of water open hot water faucets to let the air out of the water heater and plumbing system Leave the faucets open until a constant flow of water is obtained 4 Check all of the plumbing conn...

Страница 10: ...e past treated with chemicals for cleaning or sealing the system 3 If this water heater is to be used for space heating make sure that all safety codes are respected Pay special attention to safety va...

Страница 11: ...hood been installed correctly L Is the vent piping made of an approved material and sized correctly L Has the venting been installed with 1 4 inch rise per foot 21 mm m of horizontal run L Has all th...

Страница 12: ...mmediately call a qualified service technician to inspect the water heater and to replace any part of the control system and any gas control which has been under water 1 STOP Read the safety informati...

Страница 13: ...Turn the temperature dial clockwise to decrease the temperature or counterclockwise to increase the temperature The reference mark on the temperature dial indicated by a large triangle represents 130...

Страница 14: ...connections to make sure they are not leaking Main Burner Pilot Every three 3 months check the main burner and pilot flame Remove the outer access door and look through the sight glass to examine the...

Страница 15: ...2 Depress slightly and turn the gas control knob clockwise to the OFF position 3 Close the gas supply manual shut off valve 4 Close the cold water supply manual shut off valve 5 Connect one end of a g...

Страница 16: ...tube 8 Baffle 9 Flue reducer 10 Draft hood 11 Anode 12 Dip tube 13 Temperature pressure relief valve 1 Manifold Spring on some models 2 Manifold 3 Inner Left Door 4 Access Door 5 Thermal High Limit S...

Страница 17: ...control The flame burns at the orifice Low gas pressure Check with gas utility company Defective gas control Replace with new gas control The pilot will not light or remain lit No gas Check with gas u...

Страница 18: ...Condensation Water drips from the relief valve Heater stacking Lower gas control setting Excessive water pressure Install a pressure reducing valve Thermal expansion in a closed water system Install...

Страница 19: ...10 To any damage caused by not having the unit installed adjacent to a free flowing drain or in a pan or basin connected to such free flowing drain 11 For all equipment operated at water temperatures...

Страница 20: ...cted to such free flowing drain 11 For all equipment operated at water temperatures exceeding the maximum operating setting of the thermostat and or the high limit control at a pressure exceeding the...