TTM-000W Series
24 / 37
BA_MA_TTM-00XW_EN_V1.00
No. Character
Name
Description
Initial Value
16
_
mx1
Setting of the Maximum
Limit of MV Limiter
Setting Range: Minimum Limit of the MV Limiter-100.0% (110.0%)
( ) is for current output model
100.0
17
_
mL1
Setting of the Minimum
Limit of MV Limiter
Setting Range: 0.0%(-10.0%)-Maximum Limit of MV Limiter
( ) is for current output model
0.0
18
_C
1
Setting of the Control Sen-
sitivity of Output 1
Thermocouple / Resistance Temperature Detector Input Model
Setting Range: 0-999 or 0.0-999.9
Setting Unit:
℃
0
Current and Voltage Input Model
Setting Range: 0-9999 (Decimal point is at the designated position)
Setting Unit: digit
19
_ C
P1
Setting of the OFF Point of
Output 1
Thermocouple / Resistance Temperature Detector Input Model
Setting Range: -199-999 or -199.9-999.9
Setting Unit:
℃
0
Current and Voltage Input Model
Setting Range: -1999-9999 (Decimal point is at the designated po-
sition)
Setting Unit: digit
20
_
mu2
Manipulated Variable of
Output 2
It shall be used to monitor the manipulated variable of Output 2 and
to set the manipulated variable during manual control.
Display Range: 0.0-100.0
%
Setting Range: Lower Limit-Higher Limit of the MV Limiter
0.0
21
_
P2
Setting of the Proportional
Band of Output 2
Setting Range: 0.10-10.00 times
Setting Unit: Magnification for Output 1 proportional band
1.00
22
_
t2
Setting of the Proportional
Cycle of Output 2
Setting Range: 1-120 seconds
20
23
_
mx2
Setting of the Maximum
Limit of MV Limiter
(Output 2)
Setting Range: Lower Limit of the MV Limiter-100.0%
100.0
24
_
mL2
Setting of the Minimum
Limit of MV Limiter
(Output 2)
Setting Range: 0.0%-Upper Limit of the MV Limiter
0.0
25
_ C
2
Setting of the Control
Sensitivity of Output 2
Thermocouple / Resistance Temperature Detector Input Model
Setting Range: 0-999 or 0.0-999.9
Setting Unit:
℃
0
Current and Voltage Input Model
Setting Range: 0-9999 (Decimal point is at the designated position)
Setting Unit: digit