TTM-000W Series
BA_MA_TTM-00XW_EN_V1.00
23 / 37
No. Character
Name
Description
Initial Value
6
_
d1r
Switching of Direct Action /
Reverse Action
0
0
Reverse Action (heating)
1
Direct Action (cooling)
7
_
mu1
Manipulated Variable of
Output 1
It shall be used to monitor the manipulated variable of Output 1
and to set the manipulated variable during manual control.
Display Range: 0.0-100.0
%
(-10.0-110.0%)
Setting Range: Lower Limit-Upper Limit of the MV Limiter
( ) is for the current output model
0.0
8
_
tvn
Setting of Tuning Type
1
1
Auto Tuning: Output 1
2
Self Tuning: Output 1
3
Auto Tuning: Output 2
4
Self Tuning: Output 2
5
Auto Tuning: Output 1/Output 2
Auto tuning will be activated by selecting
1
/
3
/
5
and pressing
the FUNC key once. To deactivate, press the FUNC key once
while auto tuning is active.
9
_
AtG
AT Coefficient
Setting Range: 0.1-10.0
Setting Unit: Times
1.0
10
_
AT
C
AT Sensitivity
Is set up during ON/OFF
control at auto-tuning,
particularly when PV is fairly
unstable
Thermocouple / Resistance Temperature Detector Input Model
Setting Range: 0-999 or 0.0-999.9
Setting Unit:
℃
2
Current and Voltage Input Model
Setting Range: 0-9999 (Decimal point is at the designated position)
Setting Unit: digit
20
11
_
P1
Setting of the Proportional
Band of Output 1
Setting Range: 0.1-200.0%
Setting Unit: % against configured measuring range
3.0
12
_
1
Setting of Reset Time
Setting Range: 0-3600 seconds
0
13
_
d
Setting of Derivative Time Setting Range: 0-3600 seconds
0
14
_
t1
Setting of the Proportional
Cycle of Output 1
Setting Range: 1-120 seconds
20
15
_
Arw
15. Anti-Reset Windup
Takes effect of overshooting
by over-integral of PID con-
trol action.
Setting Range: 0.0-110.0
Setting Unit:
%
110.0