TTM-000W Series
22 / 37
BA_MA_TTM-00XW_EN_V1.00
6.4
Control
No. Character
Name
Description
Initial Value
1
5Et
2
Setting Mode Selection
Screen
Control Setting Mode
Settings of the Control Constant.
2
_
5LX
Setting of the Maximum
Limit of SV Limiter
Thermocouple/Resistance Temperature Detector model
Setting Range: Lower limit setting range-Upper limit setting range.
Provided that its difference from the lower limit of the SV
limiter is 50 digits or greater.
Setting Unit:
℃
1200
Current and Voltage model
Setting Range: -1999-9999 (Decimal point is at the designated
position).
Provided that its difference from the lower limit of the SV
limiter is 50 digits or greater.
Setting Unit: digit
9000
3
_
5LL
Setting of the Minimum
Limit of SV Limiter
Setting Range: Lower limit setting range-Upper limit setting range
Provided that its difference from the maximum limit of the SV
limiter is 50 digits or greater.
Setting Unit:
℃
0
Current and Voltage model
Setting Range: -1999-9999 (Decimal point is at the designated
position).
Provided that its difference from the upper limit of the SV
limiter is 50 digits or greater.
Setting Unit: digit
-1000
4
_
md
Control Mode
To be used for the setting of control mode.
rvn
: Execute the Control
rdy
: Stop the Control (Lower limit Output of the MV Limiter)
mAn
: Manual Control
rvn
5
_C
nt
Setting of Control Type
113
_C
nt
※☆
*
Function
※
Type
0
TYPE A
1
TYPE B (Overshoot Control Function)
Control Type of Output 1
☆
Type
1
PID Control
2
ON/OFF Control
Control Type of Output 2
*
Type
0
OFF
1
PID Control
2
ON/OFF Control
3
Event Output