TTM-000W Series
BA_MA_TTM-00XW_EN_V1.00
25 / 37
No. Character
Name
Description
Initial Value
26
_C
P2
Setting of the OFF Point of
Output 2
Thermocouple / Resistance Temperature Detector Input Model
Setting Range: -199-999 or -199.9-999.9
Setting Unit:
℃
0
Current and Voltage Input Model
Setting Range: -1999-9999 (Decimal point is at the designated
position)
Setting Unit: digit
27
_
Pbb
Manual Reset
Setting Range: 0.0-100.0
-100.0-100.0 (heat/cool)
Setting Unit:
%
0.0
28
_
db
Setting of Dead Band
Thermocouple/Resistance Temperature Detector Input Model
Setting Range: -100-100 or -100.0-100.0
Setting Unit:
℃
0
Current and Voltage Input Model
Setting Range: -1000-1000 (Decimal point is at the designated
position)
Setting Unit: digit
29
_
rP1
Setting of the SV Ramp
Time
Setting Range: 0.0-999.9
Setting Unit: 0.1
℃
/minute (Thermocouple/Resistance
Temperature Detector Input Model)
0.1 digit/minute (Analog input model)
Ramp function will be turned OFF if
_
rP1
=
0.0
0.0
30
_
rP2
Setting of the SV2 Ramp
Time
Setting Range: 0.0-999.9
Setting Unit: 0.1
℃
/minute (Thermocouple/Resistance Temperature
Detector Input Model)
0.1 digit/minute (Analog input model)
Ramp function will be turned OFF if
_
rP2
=
0.0
※
This will be displayed if DI is available.
0.0