E42.X.1X.6C-02
Operating Manual GIA 0420 N / GIA 010 N
page 10 of 10
11 Specifications
GIA 0420 …
GIA 010 …
Input signal:
4 ... 20 mA (2-wire)
0 ... 10 V (3-wire)
Voltage load:
3.0
– 3.5 V
(typ.)
Input resistance:
approx. 100 kOhm
max. permissible input:
25 mA
(40mA short time)
15 V
Supply voltage:
12 - 28 V
Supply current:
from current loop
< 10 mA
Display:
approx. 10 mm high LCD-display
Display range:
limits freely adjustable
Max. display value:
9999 digit
Min. display value:
-1999 digit
Recommended range:
< 2000 digit
Decimal point:
any position
Accuracy:
(at 25°C)
< 0.2% ±1 digit
Temperature drift:
< 100 ppm / K
Measuring rage:
approx. 5 measurements / second
Filter:
adjustable
Operation:
via 3 buttons
Min-/max-value memory:
callable via buttons
Switching output:
1 electrically isolated open collector output,
Test voltage: 50 V
Switching point, hysteresis:
freely adjustable
Switching voltage:
max. 28 V
Switching current:
max. 50 mA
Please note: the switching output is not short-circuits protected
Reaction time:
< 250 ms
Nominal temperature:
25 °C
Working conditions:
-20 ... 50 °C, 0 ... 80 % (non condensing)
Connection:
via 2- or 3-pin screw-type/plug-in terminal
max. wire cross selection: 1.5 mm²
Housing:
glass fibre reinforced noryl, front panel PC
24 x 48 x approx. 65 mm (H x W x D)
Panel cut-out:
21.7
+0.5
x 45
+0.5
mm (H x W)
IP rating:
IP20
by front-flush mounting: front side IP54
(IP65 by means of additional silicone o-rings)
EMC
:
The instruments confirm to following European Directives:
2014/30/EU
EMC Directive
2011/65/EU
RoHS
Applied harmonized standards:
EN 61326-1 : 2013
emissions level: class B
emi immunity according to table 3 and A.1
Additional fault: <1%
When connecting long leads adequate measures
against voltage surges have to be taken.
The device is ESD sensitive at the area of the but-
tons at the rear side
EN 50581 : 2012