Operating Manual GIA 0420 N / GIA 010 N 

page 3 of 10

 

 

Safety Requirements 

3.1  General safety advices 

This device has been designed and tested in accordance with the safety regulations for electronic devices. 
However, its trouble-free operation and reliability cannot be guaranteed unless the standard safety measures and 
special safety advises given in this manual will be adhered to when using the device

1.  Trouble-free operation and reliability of the device can only be guaranteed if the device is not subjected to any 

other climatic conditions than those stated under “Specification”. 

2.  Standard regulations for operation and safety for electrical, light and heavy current equipment have to be ob-

served, with particular attention having to be paid to national safety regulations (e.g. VDE 0100). 

3.  When connecting the device to other devices (e.g. PC) the interconnection has to be designed most thoroughly as 

internal connections in third-party devices (e.g. connection GND with protective earth) may lead to undesired volt-
age potentials. 

4.  If there is a risk whatsoever involved in running it, the device has to be switched off immediately and to be marked 

accordingly to avoid re-starting. 

 

Operator safety may be a risk if: 

 

 - there is visible damage to the device. 

 

 - the device is not working as specified. 

 

 - the device has been stored under unsuitable conditions for a longer time. 

 

In case of doubt, please return device to manufacturer for repair or maintenance. 

5.  The buttons at the rear side are necessary for the configuration of the device. 

The device is ESD sensitive at this area!!  
The configuration must be done considering adequate ESD safety measures! 

6. 

Warning: 

Do not use these products as safety or emergency stop devices or in any other application where failure of 

the product could result in personal injury or material damage. 
Failure to comply with these instructions could result in death or serious injury and material damage. 

7.  This device must not be used at potentially explosive areas! The usage of this device at potentially explosive areas 

increases danger of deflagration, explosion or fire due to sparking. 

8.  This device is not constructed for use in medical applications. 

9.  This device must not be run with a defective or damaged power supply unit. Danger to life due to electrical shock! 

3.2  Skilled Personnel 

Are persons familiar with installation, commissioning and operation of the product and have professional qualification 
relating to their job. 

For example: 

•  Training or instruction resp. Qualification to switch on or off, isolate, ground and mark electric circuits and devices 

or systems. 

 

•  Training or instruction according to the state. 

 

•  First-aid training. 

Disposal Notes 

The device must not be disposed in the unsorted municipal waste! 
Send the device directly to us (sufficiently stamped), if it should be disposed.).  
We will dispose the device appropriate and environmentally sound. 

 

 

Содержание Greisinger GIA 010 N

Страница 1: ...esstechnik GmbH Hans Sachs Str 26 93128 Regenstauf GERMANY Tel 49 9402 9383 0 info greisinger de www greisinger de Universal display for 4 20mA or 0 10V transmitter GIA 010 N as of version 1 0 Operating manual GIA 0420 N WEEE Reg Nr DE93889386 ...

Страница 2: ... 20 mA output This design type doesn t need an auxiliary supply as it is supplied by the measuring current The GIA 010 is designed for the connection of any measuring transducers with a 0 10 V output The parameters and limit values can be input by buttons accessible at the rear side The operating range of the display device can be directly adjusted to the transmitter without any additional accesso...

Страница 3: ...ble conditions for a longer time In case of doubt please return device to manufacturer for repair or maintenance 5 The buttons at the rear side are necessary for the configuration of the device The device is ESD sensitive at this area The configuration must be done considering adequate ESD safety measures 6 Warning Do not use these products as safety or emergency stop devices or in any other appli...

Страница 4: ...tion of the display device in which case we cannot assume any warranty Mind for the GIA 0420 the maximum input current rating of 40mA under any circumstances 5 1 Terminal assignment GIA 0420 N GIA 010 N connection number GIA 0420 N GIA 010 N 1 signal supply 2 signal supply GND 3 inexistent signal 4 switching output switching output 5 switching output switching output 5 2 Connection example for opt...

Страница 5: ...al 4mA D X Upper display range limit display high 1999 9999 This value is displayed for input signal 20mA L Measuring range limit OFF deactivated Exceeding of the measuring range limit is tolerable as long as value is within measuring range p r t note ON ER active display error The measuring range limit is exactly bounded by the input signal When exceeding or short falling the input signal the dev...

Страница 6: ...ng of the configuration menu 1 DEL only at outP 2P Delay of switching function of output 1 0 0 999 9 The set value is the time in seconds the device waits at least after switching off output 1 to switch it on again 1 ERR only at outP 2P Preferred position of output 1 ON OFF If an error occurs the device switches output 1 to active on or inactive off AL X only at outP AL F 1 Max alarm point AL LO D...

Страница 7: ...er Value Description Button 1 Button 2 and 3 1 ON only at outP 2P Switch on point of output 1 D LO D X Value at which output 1 should be switched on Value has to be between upper and lower measuring range limit set at the be ginning of the configuration menu 1 OFF only at outP 2P Switch off point of output 1 D LO D X Value at which output 1 should be switched off Value has to be between upper and ...

Страница 8: ...cale in The displayed value is calculated according to the following formula Display measured value offset di Lo 1 slope adjustment 100 di Lo Example for offset and slope adjustment Connection of pressure transmitter The device displays without offset and slope adjustment at 0 bar 0 08 at 20 bar 20 02 From this calculated offset 0 08 slope 20 02 0 08 19 94 difference 0 06 ideal slope actual slope ...

Страница 9: ...uration e g input signal Err 3 Display range has been exceeded Indicates that the valid display range 9999 digit of the device has been exceeded Possible causes Incorrect scale Remedies The error message will be reset if the display value is below 9999 Err 4 Values below display range Indicates that display value is below the valid display range of the device 1999 digit Possible causes Incorrect s...

Страница 10: ...Switching point hysteresis freely adjustable Switching voltage max 28 V Switching current max 50 mA Please note the switching output is not short circuits protected Reaction time 250 ms Nominal temperature 25 C Working conditions 20 50 C 0 80 non condensing Connection via 2 or 3 pin screw type plug in terminal max wire cross selection 1 5 mm Housing glass fibre reinforced noryl front panel PC 24 x...

Отзывы: