HD402…
- 20 -
V1.1
5
ALARM OPERATING MODES (HD402TR…)
Above threshold (RISE)
: the alarm is turned on if the measurement is greater than
threshold 1 for more than T1 seconds. The alarm is turned off when the measurement
becomes less then threshold 1 minus the hysteresis for more than T2 seconds.
The up arrow on the left of the display is shown when this mode is selected.
Below threshold (FALL)
: the alarm is turned on if the measurement is less than
threshold 1 for more than T1 seconds. The alarm is turned off when the measurement
becomes greater then threshold 1 plus the hysteresis for more than T2 seconds.
The down arrow on the left of the display is shown when this mode is selected.
Outside thresholds (OUTS)
: the alarm is turned on if the measurement is greater
than threshold 2 or less than threshold 1 for more than T1 seconds. The alarm is turned
off when the measurement returns between the two thresholds for more than T2 sec-
onds. No hysteresis is applied to the thresholds.
The up and down arrows on the left of the display are shown when this mode is se-
lected.