15
Mounting
Electrical installation
3-phase mains connection 480 V
4
4.3.2.1
Fusing and terminal data
Inverter
DSV35407P3
DSV35409P5
DSV3540013
DSV3540016
Cable installation in
compliance with
UL
Operation
without mains choke
Fuse
Characteristic
all acc. to UL 248/CC
all acc. to UL
248/J, T, R
Max. rated current
A
25
25
25
35
Circuit breaker
Characteristic
Max. rated current
A
25
25
25
35
Operation
with mains choke
Fuse
Characteristic
all acc. to UL 248/CC
all acc. to UL
248/J, T, R
Max. rated current
A
25
25
25
35
Circuit breaker
Characteristic
Max. rated current
A
25
35
Earth-leakage circuit
breaker
≥ 300 mA, type
B
Mains connection
Connection
X100
Connection type
Screw terminal
Min. cable cross-section AWG
16
Max. cable cross-section AWG
10
6
Stripping length
inch
0.35
0.43
Tightening torque
lb-in
4.4
11
Required tool
0.6 x 3.5
0.8 x 4.0
Motor connection
Connection
X105
Connection type
Screw terminal
Min. cable cross-section AWG
16
Max. cable cross-section AWG
10
6
Stripping length
inch
0.35
0.43
Tightening torque
lb-in
4.4
11
Required tool
0.6 x 3.5
0.8 x 4.0
PE connection
Connection
PE
Connection type
PE screw
Min. cable cross-section AWG
16
Max. cable cross-section AWG
10
6
Stripping length
inch
0.39
0.43
Tightening torque
lb-in
11
30
Required tool
0.8 x 5.5
PZ2
Содержание DSV3540013
Страница 1: ...Emotron DSV35 AC drive 4 10 hp Use in UL approved systems Mounting and switch on instruction...
Страница 2: ...This page intentionally left blank...
Страница 10: ...10 4 Mounting Mechanical installation Dimensions 10 hp All Dimensions in inch...
Страница 11: ...11 Mounting Mechanical installation 4 This page is intentionally left blank...
Страница 27: ...Technical data 6 27...