17 

Mounting

 

Electrical installation 

CANopen 

 

 

 

4.3.4

 

Modbus 

Typical topologies

 

 

 

 

Terminal description

 

 

Modbus

 

Connection 

 

X216 

Connection type 

 

Spring terminal 

Min. cable cross-section 

AWG 

22 

Max. cable cross-section 

AWG 

12 

Stripping length 

inch 

0.39 

Tightening torque 

lb-in 

Required tool 

 

0.4 x 2.5 

Basic network settings

 

Use the DIP switch to set the node address and baud rate and to activate the integrated bus terminating 

resistor. 

 

 

      R      c      b       a    128   64    32    16      8     4       2     1

 

    

                               

  

 

 

          Mode 

  Address

 

Bus termina- 

tion

 

 

Baud rate

 

Parity

 

Modbus node address

 

R

 

c

 

b

 

a

 

128

 

64

 

32

 

16

 

8

 

4

 

2

 

1

 

OFF

 

n.c. 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

Inactive 

 

Automatic detection 

Automatic detection 

Value from parameter 

ON 

ON 

ON 

Node address - example: 

Active 

Value from parameter  Value from parameter  OFF  OFF  OFF  ON  OFF  ON  ON  ON 

 

Node address = 16 + 4 + 2 + 1 = 23 

Node address > 247: value from parameter 

Printed in bold  

= Emotron setting 

 

 

 

 

The network must be terminat

ed with a 120 Ω 

resistor at the physically first and last node. 

Set the "R" switch to ON at these nodes. 

TA

 

TB   COM

 

TA

 

TA

 

TA

 

TB

 

COM

 

Line

 

A1

 

A2

 

A3

 

An

 

120 

120 

120 

120

 

X216

 

X216 

TB   COM

 

X216 

TB   COM

 

X216

 

O

Содержание DSV3540013

Страница 1: ...Emotron DSV35 AC drive 4 10 hp Use in UL approved systems Mounting and switch on instruction...

Страница 2: ...This page intentionally left blank...

Страница 3: ...cal installation 12 4 3 1 Important notes 12 4 3 2 3 phase mains connection 480 V 13 4 3 2 1 Fusing and terminal data 15 4 3 3 CANopen 16 4 3 4 Modbus 17 4 3 5 Connection of the safety module 18 4 3 5...

Страница 4: ...observe the safety instructions 1 2 Notations and conventions 1 2 1 Product code Emotron examples DSV35 40 7P3 20 DSV35 40 016 20 DSV 35 40 7P3 20 Series 3 phase 400V Rated current 7 3A IP20 DSV 35 4...

Страница 5: ...not exceed 110 VDC Observe all specifications of the corresponding documentation supplied This is the precondition forsafe and trouble free operation and for obtaining the product features specified...

Страница 6: ...motor residual movement max 180 2 90 This residual movement must be taken into consideration by the user for his her risk assessment 2 3 Application as directed The product must only be operated unde...

Страница 7: ...te and bus address CANopen Modbus PROFIBUS Motor connection PTC input X109 IT screw IT screw Network status LEDs Network X2xx Option Memory module X20 Interface X16 Diagnostic module Inverter status L...

Страница 8: ...carried out in the deenergised state After switching off the mains voltage wait for at least 3 minutes before you start working Modular construction A complete drive consists of a power unit incombina...

Страница 9: ...9 Mounting Mechanical installation 4 4 2 Mechanical installation Dimensions 4 hp 7 5 hp All Dimensions in inch...

Страница 10: ...10 4 Mounting Mechanical installation Dimensions 10 hp All Dimensions in inch...

Страница 11: ...11 Mounting Mechanical installation 4 This page is intentionally left blank...

Страница 12: ...h ground impedance must conform to the requirements of national and local industrial safety regulations and all applicable electricalcodes The integrity of all earth ground connections should be perio...

Страница 13: ...capable of delivering not more than 5 000 rmssymmetrical amperes 480 277 V maximum When protected by fuses rated as given in tablesbelow Convenient aux circuits non susceptibles de d livrer plus de 5...

Страница 14: ...4 Mounting Electrical installation 3 phase mains connection 480 V The wiring diagram is valid for Emotron DSV35inverters Fig 1 Wiring example S1 Run Stop Fx Fuses Q1 Mains contactor Dashed line optio...

Страница 15: ...istic Max ratedcurrent A 25 35 Earth leakage circuit breaker 300 mA type B Mains connection Connection X100 Connection type Screw terminal Min cable cross section AWG 16 Max cable cross section AWG 10...

Страница 16: ...b a 64 32 16 8 4 2 1 OFF OFF ON OFF ON 20 kbps OFF OFF OFF OFF OFF OFF OFF Inactive OFF OFF ON ON 50 kbps Value fromparameter ON OFF OFF ON OFF 125 kbps Node address example Active OFF OFF OFF ON 250...

Страница 17: ...6 8 4 2 1 Mode Address Bus termina tion Baud rate Parity Modbus node address R c b a 128 64 32 16 8 4 2 1 OFF n c OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Inactive Automatic detection Automatic detecti...

Страница 18: ...he EN ISO 13849 2 If an external force acts upon the drive axes additional brakes are required Please observe that hanging loads are subject to the force ofgravity The user has to ensure that the inve...

Страница 19: ...tion type Screw terminal Min cable cross section AWG 22 Max cable cross section AWG 16 Stripping length inch 0 24 Tightening torque lb in 1 8 Required tool 0 4 x 2 5 X1 Specification Unit min typ max...

Страница 20: ...a Observe safety instructions and safetyclearances 5 2 Before initial switch on Prevent injury to persons and damage to property Check the following before switching on the mains voltage Is the wiring...

Страница 21: ...ve LED status displays RDY and ERR on the front of the inverter a If the blue RDY LED is blinking and the red ERR LED is off the inverter is ready for operation The controller is inhibited You can now...

Страница 22: ...ion for the reversal of rotation direction again X3 DI3 LOW Speed characteristic example DI1 Drive follows frequencysetpoint AI1 V 10 0 DI4 Speed setpoint selection via X3 AI1 active t In this example...

Страница 23: ...esistance Overvoltage categoryIII EN 61800 5 1 0 2000 m a m s l Overvoltage categoryII above 2000 m a m s l Control circuit isolation Safe mains isolation by double reinforcedinsulation EN 61800 5 1 P...

Страница 24: ...EN 60721 3 1 Storage 2K3 25 70 C EN 60721 3 2 Transport 3K3 10 55 C EN 60721 3 3 Operation Operation at a switching frequency of 2 or 4 kHz above 45 C reduce rated output current by 2 5 C Operation a...

Страница 25: ...se mains connection 480 V The output currents apply to these operating conditions At a switching frequency of 2 kHz or 4 kHz Max ambient temperature 113 F At a switching frequency of 8 kHz or 16 kHz M...

Страница 26: ...4 4 kHz A 6 3 8 2 11 14 8 kHz A 6 3 8 2 11 14 16 kHz A 4 2 5 5 7 3 9 3 Power loss W 109 140 189 238 Overcurrent cycle 180s Max output current A 9 45 12 3 16 5 21 Overload time s 60 60 60 60 Recoveryti...

Страница 27: ...Technical data 6 27...

Страница 28: ...03 2016 13502553 1 0 01 6407 01r1 CG DRIVES AUTOMATION M rsaregatan 12 Box 222 25 SE 250 24 Helsingborg Sweden 46 42 16 99 00 Info info se cgglobal com Order order se cgglobal com...

Отзывы: