24
6
Technical data
3-phase mains connection 480 V
Standards and operating conditions
Mains current > 16 A: with mains
choke or mains filter, with
dimensioning for rated power. Rsce
≥
120 is to be met.
EN 61000-3-12
RSCE: short-circuit power ratio at the connection point
of the machine/plant to the public network.
Requirements to the shielded motor cable
Capacitance per unit length
C-core-core/C-core-shield < 75/150
pF/m
≤ 2.5 mm² /
AWG 14
C-core-core/C-core-shield < 150/300
pF/m
≥ 4 mm² /
AWG 12
Electric strength
Uo/U = 0.6/1.0 kV
Uo = r.m.s. value external conductor to PE
U = r.m.s. value external conductor/external
conductor
U ≥ 600 V
UL
Climate
1K3 (-25 ... +60 °C)
EN 60721-3-1
Storage
2K3 (-25 ... +70 °C)
EN 60721-3-2
Transport
3K3 (-10 ... +55 °C)
EN 60721-3-3
Operation
Operation at a switching frequency of 2 or 4 kHz:
above +45°C, reduce rated output current by 2.5 %/°C
Operation at a switching frequency of 8 or 16 kHz:
above +40°C, reduce rated output current by 2.5 %/°C
Site altitude
0 … 1000 m a.m.s.l.
1000 … 4000 m a.m.s.l.
Reduce rated output current by 5 %/1000 m
Pollution
Degree of pollution 2
EN 61800-5-1
Vibration resistance
Transport
2M2 (sine, shock)
EN 60721-3-2
Operation
Amplitude 1 mm
Germanischer Lloyd 5 ... 13.2 Hz
Acceleration resistant up to 0.7 g
13.2 ... 100 Hz
Amplitude 0.075 mm
EN 61800-5-1
10 ... 57 Hz
Acceleration resistant up to 1 g
57 ... 150 Hz
Noise emission
Category C1
EN 61800-3
Type-dependent, for motor cable lengths see rated
data
Category C2
Noise immunity
Meets requirement in compliance with EN 61800-3
Содержание DSV3540013
Страница 1: ...Emotron DSV35 AC drive 4 10 hp Use in UL approved systems Mounting and switch on instruction...
Страница 2: ...This page intentionally left blank...
Страница 10: ...10 4 Mounting Mechanical installation Dimensions 10 hp All Dimensions in inch...
Страница 11: ...11 Mounting Mechanical installation 4 This page is intentionally left blank...
Страница 27: ...Technical data 6 27...