36
2.7/2.8 Relay functions of X20/X21
Use menu item
2.7
to control the function of X20. Use menu
item
2.8
to control the function of X21. Both menu items have
the same options. Terminals X20 und X21 are potential-free
relay contacts.
2.7
Relay functions of X20
2.8
Relay functions of X21
►
.0
Deactivated.
. 1
Impulse of 1 second during OPEN operation at switching position.
Switching position requires teach-in with
1.7/P1.8
.
.2
Permanent contact from switching position.
Switching position requires teach-in with
1.7/P1.8
.
.3
Red light: permanent contact during door movement.
In final limit position OPEN: flashing for 3 seconds.
In final limit position CLOSE: flashing for 3 seconds.
.4
Red light: permanent contact during door movement.
In final limit position OPEN: flashing for 3 seconds.
In final limit position CLOSE: off.
.5
Flashing light: permanent contact during door movement.
In final limit position OPEN: lights up for 3 seconds.
In final limit position CLOSE: lights up for 3 seconds.
.6
Flashing light: permanent contact during door movement.
In final limit position OPEN: lights up for 3 seconds.
In final limit position CLOSE: off.
.7
Green light: off during door movement.
In final limit position OPEN: permanent contact.
In final limit position CLOSE: off.
Instead of green light, for example: usable for the clearance of a dock leveler.
.8
In final limit position CLOSE: permanent contact.
1.0
Impulse of 1 second with OPEN command.
1. 1
Impulse when switching position is exceeded.
Permanent contact when stopping in switching position.
Switching position requires teach-in with
1.7/P1.8
.