Fire Control Panel 03 – Engineers Set Up
13. Power Failure
The FCP03 can be set to trigger the Alarm sequence if Mains Power Fails and/or the
Battery Voltage is Low.
Off
Mains Failure or Low Battery Voltage does not trigger the FCP03.
Both
Mains Failure or Low Battery Voltage
triggers the FCP03 Alarm Sequence.
Low Battery
Low Battery Voltage
triggers the FCP03 Alarm Sequence. Mains Power Failure does not.
Mains
Mains Power Failure triggers the FCP03 Alarm Sequence. Low Battery Voltage
does not.
N.B. IF BOTH OR MAINS POWER FAIL IS SELECTED THE SHUTTER WILL CLOSE BY
SOLENOID OPERATION WHEN THE MAINS POWER FAILS. THE PHOTO BEAM WILL NOT
STOP THE SHUTTER FROM CLOSING.
14. Aux 2
Relay Aux 2 can be set to imitate the following functions.
Stop Relay
Close Relay
Open Relay
Trigger (Alarm) Relay
Mains Fail
Low Battery
15. PEC Alarm
ON
In normal operation if the Photo Beam remains continuously obstructed for PEC Time ‘x’
minutes the FPC03 Sounder will operate.
OFF
Photo Beam obstruction ignored.
16. Trigger Delay
ON
The Alarm signal must be present for 10 seconds before the FCP03 will activate. Can be used
to prevent nuisance tripping.
OFF
When there is a Fire Alarm signal the FCP03 activates immediately.
17. Zones
N/O
For Fire Alarm Systems providing a normally open, clean, contact held closed in Alarm.
N/C
For Fire Alarm Systems providing a normally closed, clean, contact held open in Alarm.
N.B. IF N/C is selected and only 1 Alarm Signal is connected, i.e. to Zone 1 T26 – T27, Link
Zone 2 T20 – T2.