03 Fire Door Control Systems
31
Fire Control Panel 03 – Engineers Set Up
10. Full Close End Set Up
Select the operation, ON / OFF and Flashing, of the Lamp, Sounder and Relay ‘Aux 1’
when the Shutter has Fully Closed. (The end of the Full Close Drop Time)
10a. Sign
On
The Internal and External Lamp connections are energised.
OFF
The Internal and External Lamp connections are not energised.
Flash (Option only displayed when 7a. Sign is ‘ON’)
ON
The Internal and External Lamp flashes.
OFF
The Internal and External Lamp are on ‘continuous’.
10b. Sounder
On
The Sounder is energised.
OFF
The Sounder is not energised.
10c. Aux 1
On
The Relay ‘Aux 1’ is energised.
OFF
The Relay ‘Aux 1’ is not energised.
11. Sounder
1 to 16
Select 1 of 16 different tones. This can be used to differentiate between different devices or
FCP03 panels in the same area.
12. RESET SET-UP
When the Alarms are Reset the FCP03 and Shutter can be Reset by:
Button Press
An External Push Button connected to terminals T1 and T2 or any 1 of the 3 Buttons on the
front of the panel.
Auto Reset
The Panel will Automatically Reset when the Alarm is removed and the Mains Power is on.
Re-Open Timer (Only if Reset Set-Up = Auto Reset
If the Re-Open Timer is set to 000 minutes, 000 seconds the Shutter remains closed when the
FCP03 is Reset. If a Time is set the Shutter will Automatically Open for the Time set by the Re-
Open Timer.
Содержание FCP03
Страница 1: ...10 19 FCP03 Fire Control Panel 03 INSTRUCTIONS...
Страница 2: ......