03 Fire Door Control Systems
29
Fire Control Panel 03 – Engineers Set Up
6. DOOR DELAYS
6a. Part Close Delay (Only if Closing Style = 2 Stage Drop)
On activation of Zone 1 the Part Close Delay timer starts to count down.
The shutter will start to close when the Part Close Delay time elapses.
6b. Part Close Drop (Only if Closing Style = 2 Stage Drop)
The motor control close relay is energised for the duration of the Part Close Drop time. (The
runtime to close to the Part Close position.)
The Part Close Drop timer starts once the Part Close Delay time has elapsed.
6c. Full Close Delay
If the Closing Style = 2 Stage Drop Zone 2 Alarm starts the Full Close Delay.
If the Closing Style = Full Drop Zone 1 Alarm starts the Full Close Delay.
On activation the Full Close Delay timer starts to count down.
The shutter will start to close when the Full Close Delay time elapses.
6d. Full Close Drop
The motor control close relay or the alarm solenoid relay is energised for the duration of the Full
Close Drop time. (The runtime to close to the Fully Closed position.)
The Full Close Drop timer starts once the Full Close Delay time has elapsed.
Controlling the Sign Sounder and Trigger Relay
The Sign, Sounder and Trigger Relay can be programmed to turn ON and OFF at the Start and
End of each Alarm stage.
7. PART CLOSE SET-UP (Only if Closing Style = 2 Stage Drop)
Part Close is triggered by activation of Zone 1 Alarm. Select the operation, ON / OFF and
Flashing, of the Lamp, Sounder and Relay ‘Aux 1’ during the Part Close Delay Time and
Closing movement.
7a. Sign
On
The Internal and External Lamp connections are energised.
OFF
The Internal and External Lamp connections are not energised.
Flash (Option only displayed when 7a. Sign is ‘ON’)
ON
The Internal and External Lamp flashes.
OFF
The Internal and External Lamp are on ‘continuous’.
7b. Sounder
On
The Sounder is energised.
OFF
The Sounder is not energised.
7c. Aux 1
On
The Relay ‘Aux 1’ is energised.
OFF
The Relay ‘Aux 1’ is not energised.
Содержание FCP03
Страница 1: ...10 19 FCP03 Fire Control Panel 03 INSTRUCTIONS...
Страница 2: ......