03 Fire Door Control Systems
30
Fire Control Panel 03 – Engineers Set Up
8. Part Close End Set Up
Select the operation, ON / OFF and Flashing, of the Lamp, Sounder and Relay ‘Aux 1’
when the Shutter has stopped at the Part Close Position
8a. Sign
On
The Internal and External Lamp connections are energised.
OFF
The Internal and External Lamp connections are not energised.
Flash (Option only displayed when 7a. Sign is ‘ON’)
ON
The Internal and External Lamp flashes.
OFF
The Internal and External Lamp are on ‘continuous’.
8b. Sounder
On
The Sounder is energised.
OFF
The Sounder is not energised.
8c. Aux 1
On
The Relay ‘Aux 1’ is energised.
OFF
The Relay ‘Aux 1’ is not energised.
9. Full Close Set-Up
Select the operation, ON / OFF and Flashing, of the Lamp, Sounder and Relay ‘Aux 1’
during the Full Close Delay Time and Closing movement.
9a. Sign
On
The Internal and External Lamp connections are energised.
OFF
The Internal and External Lamp connections are not energised.
Flash (Option only displayed when 7a. Sign is ‘ON’)
ON
The Internal and External Lamp flashes.
OFF
The Internal and External Lamp are on ‘continuous’.
9b. Sounder
On
The Sounder is energised.
OFF
The Sounder is not energised.
9c. Aux 1
On
The Relay ‘Aux 1’ is energised.
OFF
The Relay ‘Aux 1’ is not energised.