background image

03 Fire Door Control Systems

 

27 

Fire Control Panel 03 – Engineers Set Up 

 

 

1. DOOR TYPE - Solenoid Drop or Full Control 

Solenoid Drop 
When an Alarm is raised the Fire Shutter Alarm Solenoid is energized and the Shutter closes by 
controlled Gravity descent. 
 
Full Control 
If Mains Power is on when an Alarm is raised the Shutter closes by powered operation. (Normal 
motor driven) 
If Mains Power has failed when an Alarm is raised the Fire Shutter Alarm Solenoid is energized 
and the Shutter closes by controlled Gravity descent. 

 

2. CLOSING STYLE (Only if Door Type = Full Control) – 2 Stage Drop or Full Drop 

2 Stage Drop 
The Fire Shutter closes to a set height on activation of Zone 1 Alarm, closing completely on 
activation of Zone 2 Alarm. 
If Zone 2 Alarm is activated before Zone 1 closing to the Zone 1 position is carried out before 
the Zone 2 complete closing. 
This option is not displayed if Door Type Solenoid Drop is selected. 
 
Full Drop 
The Shutter closes in one drop. 
 

3. DOUBLE (KNOCK) NOC (Only if Closing Style = Full Drop) – Off or On 

OFF 
Ignores the Double Noc Option. 
 
ON 
Alarm Zones 1 & 2 must both be triggered before the FCP03 will activate the Alarm closing 
Sequence. 
If only one of the Zones triggers the AUX 1 relay is energised. 
This option is not displayed if Closing Style 2 Stage Drop is selected. 
 

4. SAFETY CIRCUIT-HUNTING - Ignore or Stop 

If a Photo Beam is installed this setting controls the response of the shutter during normal push 
button / key switch powered operation. 
IGNORE 
The Photo Beam does not stop the shutter during normal powered close operation. 
 
STOP 
If the Photo Beam is obstructed during normal Push Button / Key Switch powered close 
operation the Shutter will stop. 
The Shutter will continue to close when the Photo Beam is clear of obstruction and a Close 
Push Button / Key Switch is operated. 

 

Содержание FCP03

Страница 1: ...10 19 FCP03 Fire Control Panel 03 INSTRUCTIONS...

Страница 2: ......

Страница 3: ...Full Close Activation 13 Connection of Single Smoke Heat Detector for Full Close Activation 14 Connection of Two Smoke Heat Detectors for Full Close Activation 14 Fig 6e 14 Connection of Dual Alarm Zo...

Страница 4: ...oor Control Systems 4 Fire Control Panel 03 General Layout General Layout of Drives and Controls Fig 1 WARNING FIRE SHUTTER CLOSING Guthrie Douglas Guthrie Douglas WARNING FIRE SHUTTER CLOSING Guthrie...

Страница 5: ...BUTTON SC OPEN STOP CLOSE PUSH INPUT OUTPUT COMM STOP CLOSE OPEN MOTOR CONTROL AUX 1 N C C12 N O AUX 2 N C C13 N O SOLENOID 0V C18 N O ZONE 2 SC INPUT 0V PEC SC INPUT 0V ZONE 1 SC INPUT 0V 3132 2930...

Страница 6: ...2 232425 262728 RESET SC INPUT BUTTON SC OPEN STOP CLOSE PUSH INPUT COMM STOP CLOSE OPEN AUX 1 N C C12 N O AUX 2 N C C13 N O SOLENOID 0V C18 N O ZONE 2 SC INPUT 0V PEC SC INPUT 0V ZONE 1 SC INPUT 0V 3...

Страница 7: ...728 RESET SC INPUT BUTTON SC OPEN STOP CLOSE PUSH INPUT COMM STOP CLOSE OPEN AUX 1 N C C12 N O AUX 2 N C C13 N O SOLENOID 0V C18 N O ZONE 2 SC INPUT 0V PEC SC INPUT 0V ZONE 1 SC INPUT 0V 3132 2930 333...

Страница 8: ...262728 RESET SC INPUT BUTTON SC OPEN STOP CLOSE PUSH INPUT COMM STOP CLOSE OPEN AUX 1 N C C12 N O AUX 2 N C C13 N O SOLENOID 0V C18 N O ZONE 2 SC INPUT 0V PEC SC INPUT 0V ZONE 1 SC INPUT 0V 3132 2930...

Страница 9: ...PUSH INPUT OUTPUT COMM STOP CLOSE OPEN MOTOR CONTROL AUX 1 N C C12 N O AUX 2 N C C13 N O 0V C18 N O ZONE 2 SC INPUT 0V PEC SC INPUT 0V ZONE 1 SC INPUT 0V 3132 2930 3334 3536 3738 4142 4344 454647 4849...

Страница 10: ...OPEN STOP CLOSE PUSH INPUT OUTPUT COMM STOP CLOSE OPEN MOTOR CONTROL AUX 1 N C C12 N O AUX 2 N C C13 N O 0V C18 N O ZONE 2 SC INPUT 0V PEC SC INPUT 0V ZONE 1 SC INPUT 0V 3132 2930 3334 3536 3738 4142...

Страница 11: ...2 3 4 5 6 7 8 9 10 111213 141516 171819 202122 232425 262728 RESET SC INPUT BUTTON SC OPEN STOP CLOSE PUSH INPUT OUTPUT COMM STOP CLOSE OPEN MOTOR CONTROL AUX 1 N C C12 N O AUX 2 N C C13 N O SOLENOID...

Страница 12: ...sing 1 2 3 4 5 6 7 8 9 10 111213 141516 171819 202122 232425 262728 RESET SC INPUT BUTTON SC OPEN STOP CLOSE PUSH INPUT OUTPUT COMM STOP CLOSE OPEN MOTOR CONTROL AUX 1 N C C12 N O AUX 2 N C C13 N O SO...

Страница 13: ...Fig 6c 1213 141516 171819 202122 232425 262728 AUX 1 C12 N O AUX 2 N C C13 N O SOLENOID 0V C18 N O SC PEC SC INPUT 0V SC INPUT 0V F1 0A F5 F1 0A F6 F5 0A F7 INPUT 0V ZONE 2 1213 141516 171819 20 2122...

Страница 14: ...ID 0V C18 N O PEC SC INPUT 0V SC INPUT F1 0A F5 F1 0A F6 F5 0A F7 0V 0V ZONE 2 SC INPUT ZONE 1 Engineering Set up Closing Style Full Drop Double Knock Off Zones NC Link Zone 2 Terminals 20 21 1 2 3 4...

Страница 15: ...1 0A F5 F1 0A F6 F5 0A F7 INPUT 0V ZONE 2 ZONE 1 5 6 7 8 9 10 111213 141516 171819 202122 232425 262728 BUTTON STOP CLOSE PUSH INPUT OUTPUT COMM STOP CLOSE OPEN MOTOR CONTROL AUX 1 N C C12 N O AUX 2 N...

Страница 16: ...F1 0A F5 F1 0A F6 F5 0A F7 0V ZONE 2 SC INPUT ZONE 1 Engineering Set up Door Type Full Control Closing Style Two Stage Zones NC Run Time to the Part Close Position Part Close Drop Mins Minutes Part Cl...

Страница 17: ...ng Stop Obstructing the Photo Beam will Stop the Shutter from Closing by Push Button Key Switch Operation Safety Circuit Both Obstructing the Photo Beam will Stop Full Close and Part Close Alarm Seque...

Страница 18: ...Photo Beam will Stop the Shutter from Closing by Push Button Key Switch Operation Safety Circuit Both Obstructing the Photo Beam will Stop Full Close and Part Close Alarm Sequence Safety Circuit Full...

Страница 19: ...TO CHANGE THE FCP03 FUNCTIONS Press Down to scroll back through Fastset 5 to 1 From Fastset 1 press DOWN to EDIT DELAYS Press SELECT to set or change the delay timers Press DOWN from EDIT DELAYS to di...

Страница 20: ...Style 2 Stage Close X Full Drop X X X X Double Knock Off X X X X X On Safety Circuit Hunting Ignore X X X X X Stop Safety Circuit Both Full Part Ignore Off X X X X X No of Retries if applic Pause Leng...

Страница 21: ...gn Off X Sign On Flashing Off Flashing On Sounder Off X Sounder On Aux 1 Off Aux 1 On X Full Close Set Up Sign Off Sign On X X X X X Flashing Off Flashing On X X X X X Sounder Off Sounder On X X X X X...

Страница 22: ...Press Power Failure Off X X X X X Both Low Battery Mains Aux 2 Setup None X X X X Imitate Stop Relay Imitate Close Relay Imitate Open Relay X Imitate Trigger Relay Indicate Mains Failure Indicate Bat...

Страница 23: ...03 Fire Door Control Systems 23 Fire Control Panel 03 Fast Set Drawings Fast Set 1 Fig 11a Fast Set 2 Fig 11b Guthrie Douglas WARNING FIRE SHUTTER CLOSING G uthrie Douglas WARNING FIRE SHUTTER CLOSING...

Страница 24: ...03 Fire Door Control Systems 24 Fire Control Panel 03 Fast Set Drawings Fast Set 3 Fig 11c Fast Set 4 Fig 11d Guthrie Douglas WARNING FIRE SHUTTER CLOSING Guthrie Douglas WARNING FIRE SHUTTER CLOSING...

Страница 25: ...03 Fire Door Control Systems 25 Fire Control Panel 03 Fast Set Drawings Fast Set 5 Fig 11e Guthrie Douglas WARNING FIRE SHUTTER CLOSING...

Страница 26: ...03 Fire Door Control Systems 26 Fire Control Panel 03 Engineers Set Up Description of Functions Fig 12 Guthrie Douglas WARNING FIRE SHUTTER CLOSING...

Страница 27: ...is carried out before the Zone 2 complete closing This option is not displayed if Door Type Solenoid Drop is selected Full Drop The Shutter closes in one drop 3 DOUBLE KNOCK NOC Only if Closing Style...

Страница 28: ...es not stop the Shutter during Stage 2 full close sequence Further Options become available when this is set BOTH FULL or PART See below IGNORE The Photo Beam does not stop the Shutter from closing SU...

Страница 29: ...The motor control close relay or the alarm solenoid relay is energised for the duration of the Full Close Drop time The runtime to close to the Fully Closed position The Full Close Drop timer starts...

Страница 30: ...On The Sounder is energised OFF The Sounder is not energised 8c Aux 1 On The Relay Aux 1 is energised OFF The Relay Aux 1 is not energised 9 Full Close Set Up Select the operation ON OFF and Flashing...

Страница 31: ...not energised 10c Aux 1 On The Relay Aux 1 is energised OFF The Relay Aux 1 is not energised 11 Sounder 1 to 16 Select 1 of 16 different tones This can be used to differentiate between different devic...

Страница 32: ...WILL NOT STOP THE SHUTTER FROM CLOSING 14 Aux 2 Relay Aux 2 can be set to imitate the following functions Stop Relay Close Relay Open Relay Trigger Alarm Relay Mains Fail Low Battery 15 PEC Alarm ON I...

Страница 33: ...panel has not been Reset after an Alarm The FPC03 Lamp does not flash when pressing the buttons to enter Set up Engineering mode Batteries are not connected Fault Finding The Motor will not run Check...

Страница 34: ...x 1 On Part Close End Set Up Sign Off Sign On Flashing Off Flashing On Sounder Off Sounder On Aux 1 Off Aux 1 On Full Close Set Up Sign Off Sign On Flashing Off Flashing On Sounder Off Sounder On Aux...

Страница 35: ...covers and Turn On the Mains Supply 03 Fire Door Control Systems 35 WARNING FIRE SHUTTER CLOSING SELECT UP DOWN MAINS FAULT SET 1 2 3 4 5 6 7 8 9 10 111213 141516 171819 20 2122 232425 262728 RESET SC...

Страница 36: ...IAL ACCESS Supplied by GfA ELEKTROMATEN UK Ltd Agincourt Road Warwick CV34 6XZ United Kingdom Telephone 01 926 452452 Fax 01 926 336417 E mail sales gfa elektromaten co uk Web Site www gfa elektromate...

Отзывы: