7
Instruction manual
4
Place the Modbus RTU board into the free slot. Make sure that the
board is correctly snapped into the guide rails.
CAUTION
STATIC DISSIPATIVE
OBSERVE PRECAUTIONIS
FOR HANDLING
ELECTROSTATIC SENSITIVE
DEVICES
5
Insert the Modbus RTU connection cable into the cable union and
connect the glands D0, D1 and COM to the connector on the board.
The cable has to be secured against movement with the safety cap
fastenings.
Cable specification
Solid wire
26-16 AWG / 0.129-1.31 mm
2
Stranded wire
26-16 AWG / 0.129-1.31 mm
2
Torque
3.0 Lb-In / 0.34 Nm
Wire stripe length
6-7 mm
COM D0 D1
COM D0 D1
COM D0 D1
6
Set the termination-switch, located at the Modbus RTU board, to ON
•
for the last actuator in the Modbus network or
•
if there is only one actuator in the network
to activate the end termination.
ON
ON
OFF
7
Close the housing cover of the electric actuator by fixing the 4 Torx
screws.
Reconnect the power supply to power up.