5.4.8 ERRFLAGS
Label: ERRFLAGS
High Word
Low Word
Reg.# 40009 (Adr. 8)
Reg.# 40008 (Adr. 7)
Double-Word = 32Bit-Value.
<error_flags>
0 means no error/warning asserted.
Else:
Bit
Name
Description
0
undervoltage
Undervoltage condition / seven segment 'U'
1
over_temp_case
Over temperature inside EA / seven segment 'O'
2
max_positioning_time
Time monitoring / seven segment ‘S’
3
heating
Heating defect / seven segment ‘H’
4
position_detection_failed
Position learn required / seven segment 'e'
5
position_out_of_range
Position out of range: The actual measured actuator position is outside position out
of range / seven segment ‘P’
6
manual_actuation
manual actuation via handle detected / seven segment 'E'
7
accessory_no_reply
accessory option board no answer / communication timed out / seven segment '9'
8
powerfail_action
Powerfail board is in active state
9
powerfail_accu_lvl_warn
power fail intern accu level warning / seven segment ‘L’
10
powerfail_accu_defect
power fail intern accu defect error / seven segment ‘A’
11
watchdog_recovery
Restart of EA through watchdog timer warning.
12
Motor current overflow
max motor current monitoring tripped / seven segment 'I' (max_current_supervisor)
13
mot_driver_overload
error mot driver / seven segment 'b'
14 - 31
reserved
5.4.9 EACON
Electric Actuator Control Byte
Byte-Name: EACON
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Action
reserved
reserved
reserved
positioner
enabled
stop
middle
open
close
X
X
X
0
X
0
0
0
STOP
X
X
X
0
X
X
X
1
CLOSE
X
X
X
0
X
X
1
0
OPEN
X
X
X
0
X
1
0
0
MIDDLE
X
X
X
1
X
X
X
X
POSITIO-
NER_MODE
Close is dominant as it is in operation with setpoint via power input terminals.