GEZE SecuLogic emergency exit system
9.4.5 Acknowledging alarm with key switch
X
To acknowledge the alarm and lock the door, turn the key to the right.
X
To acknowledge the alarm and unlock the door, turn the key to the left and hold it for about one second.
9.5 Power failure
If the power supply is not buffered via an uninterruptible power supply, the door is not monitored and can be
passed through in the event of a power failure.
The GEZE SecuLogic emergency exit system saves the mode of operation currently set so that this is active again
after the power supply has been restored:
Mode of operation before power failure
Mode of operation after power failure
Locked
Locked
Locked by EMA
According to signal
Burglar alarm sys.
Signal active:
locked by EMA
Signal inactive:
locked
Permanent unlocking
Permanent unlocking
Short-time unlocking
Locked
Unlocked by timer
According to signal
Timer
Signal active:
unlocked
Signal inactive:
locked
Service mode
Service mode
9.6 Maintenance
The following routine maintenance checks must be carried out by the operator or an authorised representative
at intervals of no longer than one month:
à
Unlock the locking mechanisms to make sure they are not blocked.
à
Check that the door has not had any locking mechanisms fitted to it later.
à
Check that the door opening is free of obstacles that could prevent the door opening completely.
Once a year, check whether all the components of the emergency exit comply with the list of approved compo-
nents originally delivered with the system.
Have doors with electric locking mechanisms on rescue routes inspected annually by an expert. This expert
must issue a certificate of the recurring inspection, which the operator must submit to the building supervisory
authority on request. The inspection can be carried out by GEZE Service within the context of a maintenance
contract or by a specialist company authorised by GEZE.
EltVTR
EN 13637