GEZE SecuLogic emergency exit system
6
Installation of door control unit TZ 32x and door terminal T 320
6.1 Position of the emergency push button
EltVTR
Installation height above FF
Distance to the main closing edge of the door
850 mm to 1200 mm
no requirement
Attach the emergency exit sign in such a way that the arrow is pointing towards the emergency push button.
EN 13637
Installation height above FF
Distance to the main closing edge of the door
800 mm to 1200 mm
less than 600 mm
For this reason, GEZE recommends this position for the emergency push button to comply with the requirements
from EltVTR and DIN EN 13637:2015:
1 200 mm
850 mm
90°
600 mm
1 200 mm
850 mm
90°
600 mm
In the case of double-leaf doors, the distance 600 mm refers to the secondary closing edge of the active leaf.
6.2 Replacing the lock cylinder
The lock cylinder installed in the door control unit or the door terminal can be replaced by an on-site
lock cylinder:
à
Euro profile half cylinder / 40 mm (30 mm/10mm) / 8-fold adjustment
X
Undo the cylinder head screw (1),
X
Replace the Euro profile half cylinder and
X
Fasten with cylinder head screw
1