56
GEZE SecuLogic emergency exit system
1s
t l
ev
el 2nd level
3rd level
4th level
5th level
6th level
Selection
(factory setting)
Comments
Param.
inputs
Control unit
input 1
Configuration
TZ1
Selection
Sabotage ext.
Sabotage alarm and message - level
Unlock
System goes into unlocked state - flank
Lock
System goes into locked state - flank
Short-time
unlocking
System goes into short-term unlocked state -
flank
Burglar alarm sys.
EMA message becomes active. System is locked
with priority. Authorised passage is no longer
possible, disconnection and emergency unlock-
ing are still possible. Several door control units
can be locked via bus function - level
Timer
ZSU message becomes active. System goes
into unlocked state: Several door control units
can be unlocked via bus function - level
Fire alarm sys.
BMA message becomes active. System is emer-
gency unlocked. Several door control units can
be unlocked via bus function - level
Cylinder cont.
Input for lock with cylinder contact for control-
ling the door control unit or acknowledgement
of alarms (for door control units without key
switch, 1-box solution) - length of contact
is evaluated
Door handle
Input for door handle contacts for triggering
a pre-alarm when the door handle is pressed -
level
National holiday
Timer is switched off - level
Lock level
Door locks as soon as input is active. Door
unlocks as soon as the input is no longer ac-
tive. If the system is locked before the input
is activated, it remains in the locked state when
the signal goes (application e.g. for dementia
control) - level
External fault
If the input is active, the fault is signalled both
optically and acoustically and the signal is out-
putted to the bus system (application e.g. over-
riding fault signal of a UPS system) - level
Group lock
System goes into locked state. Several door
control units can be locked via bus function -
flank
Group unlock
System goes into unlocked state. Several door
control units can be unlocked via bus function -
flank
Acknowledge
alarm
Level: as long as input active
Flank: as soon input becomes active
Type of level TZ1 Selection
High active
Low active
Deactivated
Input active (is evaluated) when 24 VDC are
applied (normally open contact)
Input active (is evaluated) when 0 VDC are ap-
plied (normally closed contact)
No evaluation of the input
Control unit
input 2
Configuration
TZ2
Selection
Short-time
unlocking
cf. Control unit input 1
Type of level TZ2 Selection
High active
cf. Control unit input 1
Control unit
input 3
Configuration
TZ3
Selection
Fire alarm sys.
cf. Control unit input 1
Type of level TZ3 Selection
High active
cf. Control unit input 1
Param.
outputs
Control unit
output 1
Configuration
TZ1
Selection
Door state
Contact is closed when door is closed.
BA. drive
Contact is closed when door control unit is per-
manently unlocked.
Activ. drive
Contact closes for 3 seconds when short-time
unlocking has been triggered (even if system
is unlocked).
In the case of disconnection or emergency
unlocking the contact remains closed until the
alarm is ended.
Alarm
Contact closes with all alarms (except pre-
alarm).
Disconnection
Contact closes when the emergency push
button is pressed on the TZ 320 and indirect
disconnection.