61
GEZE SecuLogic emergency exit system
1s
t l
ev
el 2nd level
3rd level
4th level
5th level
6th level
Selection
(factory setting)
Comments
active
In the basic state, all the doors are locked and
closed. Only one door at a time in the security
interlocking door group can be unlocked short-
term. This prevents the short-time unlocking of
another door in the security interlocking door
group via the bus.
If a door is permanently unlocked, the inter-
locking function is switched off at this door.
The interlocking function is switched back on
again by locking the door.
The doors must be locked when the interlock-
ing door system is put into operation.
Emergency unlocking is possible at any time.
The emergency push button only acts on the
respective door.
Assignment
Security inter-
locking door
group 1:
Selection
assigned
Yes
No
Ten security interlocking door groups each with up
to 63 devices can be formed within one bus line.
If active and passive interlocking door systems
are mixed within one security interlocking door
group:
- The opening of a passive door blocks the
short-time unlocking of the active doors.
- The short-time unlocking of an active door
locks all the passive doors.
Security inter-
locking door
group 2:
Selection
assigned
Yes
No
Security inter-
locking door
group 3:
Selection
assigned
Yes
No
Security inter-
locking door
group 4:
Selection
assigned
Yes
No
Security inter-
locking door
group 5:
Selection
assigned
Yes
No
Security inter-
locking door
group 6:
Selection
assigned
Yes
No
Security inter-
locking door
group 7:
Selection
assigned
Yes
No
Security inter-
locking door
group 8:
Selection
assigned
Yes
No
Security inter-
locking door
group 9:
Selection
assigned
Yes
No
Security inter-
locking door
group 10:
Selection
assigned
Yes
No
Re-locking
Change value
0 s
1 s
…
5 min
In order to balance pressure in an interlock-
ing door system it can be necessary for the
interlocking door system to remain locked for
a certain time after passage.
If the opened door of a security interlocking
door group is closed again, all the door control
units in the group go into the state
Interlocking
door system occupied
for the time set.
Different times can be set at the door control
units of one group.
The re-locking time of the door control unit that
has been opened always applies. Re-locking
also becomes active if a door has been short-
term unlocked but not opened.
Group lock/
unlock
Selection
permitted via bus
Yes
No
All the door control units on one bus line can be
unlocked or locked via inputs of one door control
unit. For this, the inputs to which the signals are
connected must be configured to Group unlock
or Group lock.
The door control unit sends the signals to the bus.
In the factory setting, each door control unit on
the bus responds to these signals.
This function must be deactivated at a door con-
trol unit which is not to respond to these signals.
Unlocking and locking this door control unit via
the panel TE 220 is then no longer possible either.