INSTALLATION INSTRUCTIONS
56
UP
UP
Shield
Electrical continuity
conductor
Bus cable
Bus
230 V
≥ 4 mm
Mounting on a round (or square) box
1. The length of the bus line between the Easy thermostat and the power supply unit must
not exceed 350 metres.
2. The length of the bus line between the Easy thermostat and the most distant KNX/EIB
device must not exceed 700 metres.
3. If possible do not create ring circuits so as to prevent undesirable signals and
overloads.
4. Keep a distance of at least 4mm between the individually insulated cables of the bus
line and those of the electric line.
5. Do not damage the electrical continuity conductor of the shielding.
Warnings for KNX/EIB installations