FAN COIL CONTROL
When the temperature reaches the set point value-
(in heating) or set point+
(in air-conditioning) an ON
message is sent to activate the fan coil for the selected
operation type, and an ON message to switch on the fan
coil at speed V1.
At set point-2
(in heat.) or set point +2
(in air-cond.)
speed V2 is activated, at set point-3
(in heat.) or set
point+3
(in air-cond.) speed V3 is activated.
V3
V2
V1
Fan OFF
-2
-3
-
T
set point
Fan Coil OFF
Fan Coil ON
V3
V2
V1
Fan OFF
+2
+3
+
set point
Fan Coil ON
Fan Coil OFF
T