29
URS 60, URS 61 - Installation & Operating Manual -
819634-00
Bringing into service – start, operation, alarm and test
Fig. 12
Assignment of button/signal LED/limiter:
Button 1/LED 1: Limiter 1
Button 2/LED 2: Limiter 2
Button 3/LED 3: Limiter 3
Button 4/LED 4: Limiter 4
The following table is based on four activated limiter functions.
Start
Switch on
supply voltage.
All LEDs light up
The system is started and tested.
The output contacts open.
The signal outputs close (lamp test).
Operation
Limiters 1 – 4 do not
signal an alarm
Signal LEDs 1 – 4
light up green
The output contacts close,
the signal outputs open.
Alarm
Limiters 1 – 4,
one or more
signal an alarm
Signal LED 1, 2, 3, 4,
one or more flash red rapidly
The switch-off delay is running, the signal output
closes with/without a delay.
Signal LED 1, 2, 3, 4,
one or more light up red
The delay time has elapsed,
the output contacts open.
The signal outputs close.
Test of limiters 1 – 4
In operating mode:
Press button 1, 2, 3 or 4 and
hold until the end of the test.
The limiters must behave as if
there were an alarm.
Signal LED 1, 2, 3 or 4
flash red rapidly
Alarm simulation in limiters 1 − 4.
The switch-off delay is running, the signal output
closes with/without a delay.
Signal LED 1, 2, 3 or 4
lights up red
The delay time has elapsed, the output contacts
open.
The signal output closes.
The test ends.
LEDs 1 to 3 (yellow), indication of system malfunctions, see page 32
Membrane keys 1 to 4,
incl. standby display (green)/status display (red)
Содержание URS 60
Страница 1: ...Original Installation Operating Manual EN English Safety Control Unit URS 60 URS 61 819634 00 ...
Страница 37: ...37 URS 60 URS 61 Installation Operating Manual 819634 00 For your notes ...
Страница 38: ...38 URS 60 URS 61 Installation Operating Manual 819634 00 ...
Страница 39: ...39 URS 60 URS 61 Installation Operating Manual 819634 00 ...