URS 60, URS 61 - Installation & Operating Manual -
819634-00
Changing the equipment settings
The URS 60 / URS 61 safety control units are designed for up to four limiter functions for monitoring water
level, temperature and conductivity. You can connect level electrodes NRG 1x-6x or NRG 26-61, tempera-
ture transmitter TRV 5-60 and conductivity electrode LRG 1x-6x.
For operation, you must define the number of limiter functions you wish the control units to work with. Set
the limiting function you require by connecting the various sensors for level, temperature and conductivity
and by assigning the necessary parameters.
With the lower terminal strip removed:
Using a thin-blade screwdriver, configure the code switch
D
(see
Fig. 9
) using switches S1 to S10 as
shown in the table. Next, re-install the terminal strip and tighten the fastening screws.
Code switch
D
-
sliding switch, white
1
ON
2 3 4 5 6 7 8 9 10
Configuring the limiter function
URS 60 / URS 61 safety control unit
Code switch
D
Limiter functions 1 to 4
(see Fig. 5)
S1
S2
S3
S4
S5
S6
S7
S8
>
1
2
3
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
>
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
>
Active
ON
ON
ON
ON
OFF
OFF
OFF
OFF
>
Active
Active
ON
ON
ON
ON
ON
ON
OFF
OFF
>
Active
Active
Active
ON
ON
ON
ON
ON
ON
ON
ON
>
Active
Active
Active
Active
Factory setting of URS 60
ON
ON
ON
ON
OFF
OFF
OFF
OFF
>
Active
Active
Factory setting of URS 61
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
>
Active
Содержание URS 60
Страница 1: ...Original Installation Operating Manual EN English Safety Control Unit URS 60 URS 61 819634 00 ...
Страница 37: ...37 URS 60 URS 61 Installation Operating Manual 819634 00 For your notes ...
Страница 38: ...38 URS 60 URS 61 Installation Operating Manual 819634 00 ...
Страница 39: ...39 URS 60 URS 61 Installation Operating Manual 819634 00 ...