12
URS 60, URS 61 - Installation & Operating Manual -
819634-00
Functional safety, safety integrity level (SIL)
The URS 60 / URS 61 safety control unit is suitable for safety functions up to SIL 3.
It is an element of a safety circuit up to SIL 3 as per EN 61508 in the SPECTOR
connect system, and can
process alarm information from up to four safety sensors.
Combinations with accessories constitute a type B subsystem. The technical and safety characteristics in
Fig. 4 are based on the URS 60 / URS 61 safety control unit including output contacts.
Breakdown of safety function failure rates
Sensor
probe
The CANopen interface is a “Black Channel” type, and can be ignored during calculation due to
the low failure rate of < 1FIT.
CANopen
URS 60,
URS 61
Burner safety circuit
Sensor
electronics
Fig. 3
Perform an annual function test
Check the function of the URS 60 / URS 61 safety control unit at least once annually by triggering the
safety circuit (T1 = 1 year). You can check the function either by pressing buttons 1-4 (see page 29) or
by exceeding the limit values.