26
URS 60, URS 61 - Installation & Operating Manual -
819634-00
Changing the equipment settings
DANGER
There is a risk of electric shock during work on electrical systems.
■
■
Always switch off the voltage to the equipment before performing work on the terminal
strips.
■
■
Check that the system is not carrying live voltage before commencing work.
Changing the baud rate
Set the baud rate using the code switch
D
Fig. 9
(S9), see page 28.
You must set the same baud rate for all bus participants.
You can change the factory settings of URS 60 / URS 61 safety control units at any time.
Make changes before installing the safety control unit, when access is easier.
You will need the following tools:
■
■
Slotted screwdriver, size 2.5
■
■
Phillips screwdriver, size 1
Proceed as follows:
1.
Unscrew and pull off the lower terminal strip, see
Fig. 9
.
2.
Set the code switch
D
(see
Fig. 9
) as desired, see page 27 and 28.
3.
Put the terminal strip back on and screw in place.