17
Factory setting
Spector
control
All adjustable masks are fully available, regardless of whether or not the indicated instruments are part
of the bus system. Subsequent expansion or modification is therefore possible at any time.
The SPECTOR
control
runtime licence can be found on the rear of the unit. If you need to re-enter this
licence but the label is no longer on the unit, please request it from GESTRA Bremen.
The inputs/outputs of the WAGO I/O module can only be defined after you have entered the number of
terminals in [SPECTORcontrol]/System/IO Module.
The system settings for initial startup are stored on the CompactFlash. Data are also stored on the CF
card during operation of the SC, in the /DATA folder.
The equipment features the following default settings:
■
Date/time
Current date and time (daylight saving time: disabled)
■
Home screen
Home screen 1 (1..4 to be defined as desired)
■
Language
German
■
IP address 1 (Ether 1)
192.168.0.99
■
IP address 2 (Ether 2)
can be freely assigned
■
Passwords
Level 1: aaa
Level
2:
bbb
■
Node ID SC
127
■
Node ID of WAGO I/O
126
■
Baud rate
250 kB
■
Profibus station address
10 (slave), other arrangements possible on request
Note
We recommend using new passwords after initial startup!
Make sure that the same password is not used twice.
The maximum length of the password is 8 characters.
Bringing into service
Switching on the supply voltage
Switch on the supply voltage for the SPECTOR
control
. Home screen 1 opens.
Attention
■
Please pay attention to the Installation & Operating Manuals of the connected
equipment.