26
System malfunctions
Display of system malfunctions in the alarm and error list using fault codes
Fault codes for the URS 60/URS 61 safety control unit
Fault code
Internal
designation
Possible faults
Remedy
E.006
ProbeCntErr
No electrode configured Check code switch
E.007
DipKonfErr
Inconsistent code
switch setting
Check code switch
E.008
Ch1Ch2DiffErr
EMC or internal error
Check installation location
Replace safety control unit
E.009
Relais1Err
Error in relay 1
Check installation location
Replace safety control unit
E.010
Relais2Err
Error in relay 2
Check installation location
Replace safety control unit
E.012
DoubleStandByErr
Two electrodes are
bridged
Check both monitoring units (SRL 6-60)
E.013
Probe1Err
Collective fault in
channel 1
Check channel 1
E.014
Probe2Err
Collective fault in
channel 2
Check channel 2
E.015
Probe3Err
Collective fault in
channel 3
Check channel 3
E.016
Probe4Err
Collective fault in
channel 4
Check channel 4
E.019
V6Err
EMC or
voltage error
Check installation location
Replace safety control unit
E.020
V5Err
EMC or
voltage error
Check installation location
Replace safety control unit
E.021
V3Err
EMC or
voltage error
Check installation location
Replace safety control unit
E.022
V1Err
EMC or
voltage error
Check installation location
Replace safety control unit
E.023
V12Err
EMC or
voltage error
Check installation location
Replace safety control unit
E.024
CANErr
Wrong baud rate or
wiring error
Check the baud rate, wiring and
terminating resistors
E.025
ESMG1 (μC1Err)
EMC error or internal
process error
Check installation location
Replace safety control unit
E.026
BIST (SelftestErr)
EMC or internal error
Check installation location
Replace safety control unit
All fault codes from E.001 to E.027 not listed here are available as reserves