36
System Malfunctions
– continued –
Fault:
Data transfer between switching controller and electrode interrupted.
Remedy:
The bus cables have to be connected correctly according to the wiring diagram
(observe polarity!).
Make sure that all endofline nodes are provided with 120 Ω terminating
resistors. Cut off power supply and restart system after 5 sec.
Fault:
The baud rate of one or more nodes is not set correctly.
Remedy:
Check baud rate settings of all bus nodes. The baud rates must be identical.
Cut off power supply and restart system after 5 sec.
Fault:
The overall length of the bus cable does not correspond to the selected baud rate.
Remedy:
Change baud rate settings of all nodes accordingly.
Cut off power supply and restart system after 5 sec.
Fault:
The electronic circuit board of the equipment is defective.
Remedy:
Replace the equipment. Restart the system.
Error message 6
1
2
3
4
Test
P
1
2
3
E
4
GESTRA
NRS 1-40
Error message 7
Fault:
The power supply unit (PSU) is overloaded. The power supply unit may be misused for
other components.
Remedy:
Check load of power supply unit. Be sure to use the PSU only for the voltage supply of
busbased network components.
Cut off power supply and restart the system after 5 sec.
Fault:
Power supply unit defective.
Remedy:
Replace power supply unit.
LEDs 1 to 4 are flashing slowly and/or
LED “Bus status” is flashing slowly.
LED “Power” is flashing slowly.
Содержание NRS 1-40
Страница 1: ...1 E N English Switching Controller NRS 1 40 Original Installation Instructions 810635 07 ...
Страница 10: ...10 Technical Data continued Dimensions Fig 2 1 1 8 100 73 ...
Страница 11: ...11 Design NRS 1 40 Fig 3 0 0 ...
Страница 12: ...12 Functional Elements NRS 1 40 Fig 5 8 9 Fig 4 1 7 6 5 4 3 2 ...
Страница 15: ...15 Installation continued Example of installation Fig 6 0 0 Fig 7 20 20 ...
Страница 38: ...38 For your notes ...
Страница 39: ...39 For your notes ...