33
System Malfunctions
– continued –
Error message 3
LED 3 is flashing slowly.
A malfunction in the bus communication
between level switch and
level electrode 1
has
been detected.
Hold down button
.
LED 1 is flashing rapidly.
Fault:
Bus lines C
L
and C
H
are interchanged.
Remedy:
Connect bus lines according to the wiring diagram.
Fault:
The operating mode setting is not correct: Water level limiter (
one
level electrode)
or water level limiting system (
two
electrodes).
Remedy:
Check and, if necessary, correct the settings in the switching controller and
the sensor.
Fault:
The data transfer between level switch and electrode is interrupted.
Remedy:
Make sure that the bus lines are wired in accordance with the wiring diagram
(observe polarity). All endofline devices must be provided with a terminating
resistor of 120 Ω (see wiring diagram). Cut off power supply and restart the
system after 5 sec.
Fault:
The baud rate of one or more bus devices is not set correctly.
Remedy:
Check baud rate settings of all bus devices.
The baud rate settings must be identical.
Cut off power supply and restart the system after 5 sec.
Fault:
The overall length of the bus line does not correspond to the baud rate setting.
Remedy:
Change baud rate settings of all bus based equipment.
Cut off power supply and restart the system after 5 sec.
Fault:
In spite of correct wiring and commissioning of the equipment an interference
signal is indicated.
Remedy:
The interference signal is caused by H. F. interferences coming from the installation.
For interference suppression of the voltage supply we supply ferrite rings, stock
code 147253. The 230 V supply lines should be looped through the ferrite ring
five to ten times. If several controllers are used in the system, they can be fed
from the interference suppressed supply lines. For the interference suppression
of the bus line we supply hingedshell ferrite rings, stock code 147254.
The hingedshell ferrite rings are clamped onto the bus line close to the terminal
strip of the controller. Restart the system after installation.
A
Содержание NRS 1-40
Страница 1: ...1 E N English Switching Controller NRS 1 40 Original Installation Instructions 810635 07 ...
Страница 10: ...10 Technical Data continued Dimensions Fig 2 1 1 8 100 73 ...
Страница 11: ...11 Design NRS 1 40 Fig 3 0 0 ...
Страница 12: ...12 Functional Elements NRS 1 40 Fig 5 8 9 Fig 4 1 7 6 5 4 3 2 ...
Страница 15: ...15 Installation continued Example of installation Fig 6 0 0 Fig 7 20 20 ...
Страница 38: ...38 For your notes ...
Страница 39: ...39 For your notes ...