32
System Malfunctions
– continued –
Error message 2
LED 2 is flashing slowly.
A system malfunction in
level electrode 2
was detected.
Hold down button
.
LED 1 and 2 are flashing slowly.
Hold down button
.
LED 2 is flashing slowly.
Fault:
The max. admissible temperature in the terminal box of the electrode has
been exceeded.
Remedy:
Insulate electrode flange against thermal radiation.
Fault:
The electronic circuit board of the level electrode is defective.
Remedy:
Replace the electronic circuit board of the level electrode 2.