Installation examples with dimensions
Key
g
Flange NPS 2 (DN 50) NPS 4 (DN100)
(for 2 electrodes)
h
Perform preliminary inspection of
standpipe and flange during the
boiler inspection.
i
Pressure relief hole
Locate hole as close to boiler
wall as possible!
j
Electrode rod d = 0.32 in (8 mm)
k
Protective foam tube/level pot
l
Low water LW
m
Reducer
n
High water HW
o
Electrode spacing
≥
0.55 in (14 mm)
(air gaps and creepage paths)
CD Center distance of standpipes
Fig. 19
Level pot if electrode is used as an
external high-level alarm
1" - 11.5 NPT
g
n
l
m
CD
h
o
j
k
Pipe diameter
(DN)
≥
Pipe diameter/2
(
≥
DN/2)
≥
Pipe diameter/2
(
≥
DN/2)
Pipe diameter
(DN)
Connecting pipe shall not
be smaller than 1" NPS.
No shut-off valve of any
type shall be placed in
the piping between the
boiler and the low water
cutoff.