24
NRG 16-51, NRG 17-51, NRG 19-51 - USA - Installation & Operating Manual -
850692-00
Installing the NRG 16-51F, NRG 17-51F, NRG 19-51F, additional information
If you are installing an NRG 1...-51F level electrode in a protective tube or level pot together with
a level electrode, level switch or transmitter (with aluminum terminal box), please note the fol-
lowing:
1. Install the first unit as described in the relevant Installation & Operating Manual.
Then, please note the following for installing the NRG 1...-51F level electrode:
1. Undo the screws
b
and take off the cover
d
of the terminal box.
Fig. 15.
The arrow on this
cover points to the rating plate.
2. Remove the cable lugs from the pins.
Fig. 15
3. Slacken the nut
e
using a size 19 open-ended wrench. Do not unscrew completely!
Fig. 16
4. Screw in the level electrode as described in step 2, points 7 - 10 below.
5. Rotate the terminal box in the desired direction (+/–180 °).
The terminal box can be r/–180°.
ATTENTION
Rotating the terminal box ≥ 180° will damage the internal wiring of
the NRG 16-51F, NRG 17-51F, NRG 19-51F level electrodes.
■
Never rotate the terminal box more than 180° in either direction.
6. Tighten the nut
e
to
25 Nm
.
7. Push the cable lugs back onto the pins.
8. Fit the cover
d
of the terminal box and tighten the screws
b
.
Installation
b
Terminal box screws M 4
c
Cable gland M 20 x 1.5
d
Terminal box cover
e
Nut
f
Terminal strip
Key