30
LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual -
850702-01
Operation, alarm and test
Conductivity controller LRR 1-50, LRR 1-51:
Checking indications and the function of the MAX output contact
Operation
Action
Indication
Function
Actual value < set
point
The actual value is shown on
the 7-segment display.
LED 2 for valve closing flashes,
MAX LED is not lit.
Valve output contact 19/17 closed, MAX output
contact 21/23 open, 22/23 closed.
Test of MAX alarm
Action
Indication
Function
In operating mode:
Actual value < set point.
Select Test parameter. Press
and hold push-button. 7-seg-
ment display: Test flashes.
MAX LED lights up red for 3
seconds
MAX output contact 21/23 closed,
22/23 open.
After 3 seconds:
MAX LED goes out.
MAX output contact 21/23 open, 22/23
closed.
Test complete, release
push-button. 7-segment dis-
play: Test is displayed.
Note: If you continue holding the push-button, the test sequence will start
again. You can cancel the test sequence at any time by releasing the
push-button.
Turn the rotary knob until the actual value is displayed.
Or after 30 s, the actual value is displayed automatically.
Note
The continuous blowdown valve has three limit switches for the CLOSED, OPEN and
OPERATING positions. In OPERATING position, the continuous blowdown valve is
slightly open. This enables a certain blowdown volume to be removed from the boil-
er, to keep the TDS below the limit. The blowdown volume is established using the
capacity charts of the continuous blowdown valve. Please refer to the Installation &
Operating Manual for GESTRA continuous blowdown valves.
Set point exceeded
Actual value > set
point
The actual value is shown on
the 7-segment display.
1. LED 1 for valve opening
flashes
2. LED 2 for valve closing
flashes, MAX LED is not lit.
Continuous blowdown valve opens. After the
conductivity has fallen by the set hysteresis
HySt, the valve moves into OPERATING position.
1. Valve output contact 19/16 closed.
2. Valve output contact 19/17 closed.
MAX output contact 21/23 open,
22/23 closed.
MAX alarm
Conductivity above MAX
switchpoint.
MAX LED lights up red
MAX output contacts 21/23 closed, 22/23
open.
Standby
Burner is switched off (standby)
Supply voltage for conductivity controller is also switched off.
When they are switched on again, the system restarts. See
page 18
Valve output contact 19/18 closed.
Continuous blowdown valve closes.