29
LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual -
850702-01
Bringing into service
Conductivity controller LRR 1-51: Setting switchpoints and parameters
Setting the MAX switchpoint
Action
Function
Select parameter AL.Hi, enter and save the
desired conductivity.
The MAX switchpoint is set between
1 and 5000 ppm or 1 and 9999 µS/cm.
Setting the set point
Select parameter SP, enter and save the desired
conductivity.
The set point is set between
1 and 5000 ppm or 1 and 9999 µS/cm.
Setting the reset hysteresis
Select parameter HySt, enter and save the
required value.
The reset hysteresis is set between 1 and 25% of the set
point.
Setting the lower and upper ends of measuring range
Select parameter Sin.L, enter and save the
desired conductivity.
Lower end of measuring range is set in stages
0.0 - 0.25 - 25 - 50 ppm (0.0 - 0.5 - 50 - 100 µS/cm)
Select parameter Sin.H, enter and save the
desired conductivity.
Upper end of measuring range is set in stages
10 - 50 - 100 - 250 - 500 - 1000 - 1500 - 2500 - 3000 -
3500 - 5000 - 6000 ppm
(20 - 100 - 200 - 500 -1000 - 2000 -
3000 - 5000 - 6000 - 7000 - 10000 - 12000 μS/cm)
Setting the actual value output-current output standardization
Select parameter Sout, enter and save the
desired conductivity.
The current output is set between
5 and 5000 ppm (10 and 9999 µS/cm)
Setting the flushing interval and flushing time
Select parameter Si, enter and save the desired
time.
The flushing interval is set between 0 and 24 hours.
Select parameter Sd, enter and save the
desired time.
The flushing time is set between 1 and 4 minutes.
Fig. 6
Rotary knob with
integrated
push-button
Red MAX LED
7-segment display
LED 1 for
valve opening
LED 2 for
valve closing