26
LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual -
850702-01
Starting
Action
Indication
Function
Switch on supply
voltage.
7-segment display shows soft-
ware/equipment version
System test, takes approx. 3 s.
7-segment display shows actual
value, LEDs light up.
Switch to operating mode
Actual value < set point 1. LED 1 for valve opening flashes
2. LED 2 for valve closing flashes.
Continuous blowdown valve opens for time Sd
then moves into OPERATING position.
Actual value > set point 1. LED 1 for valve opening flashes
2. LED 2 for valve closing flashes.
Continuous blowdown valve opens. After the
conductivity has fallen by the set hysteresis
HySt, the valve moves into OPERATING position.
Setting parameters
Action
7-segment display
Function
Turn rotary knob until de-
sired parameter is shown
Display toggles between
parameter and saved value.
The parameter is selected
Press and hold the
push-button (on rotary knob) First digit (000
0)
flashes.
Parameterization mode active. You can change
the first digit.
Turn rotary knob
A new value is displayed.
Turning clockwise increases the value, turning
counterclockwise reduces the value.
Briefly press the push-but-
ton. The digit increases with
each press
2nd, 3rd or 4th digit flashes
(from right to left).
2nd, 3rd or 4th digit can now be changed using
the rotary knob. Turning clockwise increases
the value, turning counterclockwise reduces
the value
If you take no further action:
quit is briefly displayed.
After this, the display toggles
between the parameter and
the old value.
The system automatically returns to parameter
settings and your entry is not confirmed.
When your entries are
complete: Press and hold
the push-button
done is briefly displayed.
After this, the display toggles
between the parameter and
the new value.
Your entry is confirmed and the system auto-
matically returns to parameter settings.
Turn the rotary knob until the next parameter is shown.
Or turn the rotary knob until the actual value is displayed.
Or after 30 s, the actual value is displayed automatically.
Bringing into service
Setting parameters
Fig. 6
Rotary knob with
integrated
push-button
Red MAX LED
7-segment display
LED 1 for
valve opening
LED 2 for
valve closing
If
password protection
is enabled, you must enter the password before changing a
parameter. See section on password protection.