13
LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual -
850702-01
Factory default settings
Conductivity controller LRR 1-50
■
MAX switchpoint AL.Hi =
3000 ppm (6000 µS/cm)
■
Set point SP = 1500 ppm (3000 µS/cm)
■
Dead band: +/– 5% of set point
■
Reset hysteresis:
Set point: –10% of set point
MAX limit: –3% (fixed setting)
■
Correction factor CF = 1
■
Temperature compensation inP = No
■
Temperature coefficient tC = 2.1% / °C
■
Standardization of current output Sout =
3000 ppm (6000 µS/cm)
■
Operating position oPP = 5%
■
Flushing interval Si = 0 h
■
Flushing time Sd = 3 min (valve opens for 3
min
and closes for 3 min)
■
Damping FiLt: oFF
■
Password PW: oFF
■
Code switch
c
:
S1: OFF, S2: ON, S3: OFF, S4: OFF
Conductivity controller LRR 1-51
■
MAX switchpoint AL.Hi =
3000 ppm (6000 µS/cm)
■
Set point SP = 1500 ppm (3000 µS/cm)
■
Dead band: +/– 5% of set point
■
Reset hysteresis:
Set point: –10% of set point
MAX limit: –3% (fixed setting)
■
Lower end of measuring range Sin.L =
0.25 ppm (0.5 µS/cm)
■
Upper end of measuring range Sin.H =
3000 ppm (6000 µS/cm)
■
Standardization of current output Sout =
3000 ppm (6000 µS/cm)
■
Operating position oPP = 5%
■
Flushing interval Si = 0 h
■
Flushing time Sd = 3 min (valve opens for 3
min and closes for 3 min)
■
Damping FiLt: oFF
■
Password PW: oFF
■
Code switch
c
:
S1: OFF, S2: ON, S3: OFF, S4: OFF