RENTAL & SILENT ENERGY RENTAL GENSETS 4.3
59
Contacts: mechanically and electrically interlocking. They are used when the nominal current is
between 40 and 125 A.
Motorised switches: used from 160 A to 3200 A.
Motorised circuit breakers: mechanically and electrically interlocking. Supplied when requested by
the customer.
The following diagram shows the functioning of a switchboard:
Picture 38- Switchboard diagram
The electrical installation of the switchboard is divided in two parts: firstly the control part
must be installed (electrical grid monitoring and management and switching) and secondly the power
part (transmission of electrical energy).
14.3.2. Switchboard not supplied by GRUPOS ELECTRÓGENOS EUROPA S.A
Consult the user manual of the corresponding switchboard and follow these steps.
Connect the terminals R S T N of the control panel (reference voltage of the electrical grid) to the
supply input of the electric company.
Connected the terminals numbered from 37 to 47 (both inclusive) to the control wiring of the
switchboard (consult the electrical diagram of the generator set panel).
Ensure that the electrical and mechanical interlocking has been correctly executed. Ensure that the
switchboard you wish to install is compatible with the generator set supplied. Typical assembly is
with contacts. For motorised switches consult GRUPOS ELECTRÓGENOS EUROPA S.A
The section of the conductor must be suitable for your installation.