instruments or parameters on each screen menu, press
(10) or
(11) buttons. To come
back to a previous menu screen, press
(9) button.
The alarmlist screen display the alarms detected by the module. Pressing
button (4) faults
and alarms are acknowledged.
The measurement screen displays the parameters measured on the engine; if the engine uses an
electronic management system, many additional parameters can be displayed. In addition to these
parameters, measurements can be displayed for fuel level, oil pressure, current, voltage, frequency, run
hours and battery charge level.
The measurement I/O screen display the status of digital inputs and outputs and the measured
parameter of analogue inputs (senders).
The history screen menu displays the log of alarms that have occurred in the generator unit. It also
logs the opening and closing of the mains circuit breaker as well as the starting and shutting down of the
generator unit.
The set points menu screen displays the adjustment parameters already configured; it is not
necessary to edit any of these.
The users/password screen allows to define users and passwords. The languages screen allows to
change the display language
AUTOMATIC mode (AUTO):
If a mains failure is detected, the InteliGen
NT
module will open the MCB (main circuit breaker).
Startup command is issued to generator set. If generator voltage is within the established limits, the LED
indicator
(17) will be on and the control module closes the GCB (generator circuit breaker).
Once mains power has been restored, synchronization between mains and generator occurs; then the
MCB is closed, causing the generator to discharge, followed by the opening of the GCB. When mains
power is restored, there will be a period of time during which the engine continues operating at no load to
cool down before stopping completely.
Note: If
(4) is pressed following a disconnection alarm, the engine could automatically start without any warning.