Installer manual NETZERO
GEOSMART ENERGY
33
EN
Production protection
1.
Used to adjust the minimum production temperature in cooling mode. If the set
temperature is reached, the compressor stops.
2.
Used to set the minimum pressure of the production circuit, under which the alarm is
triggered.
3.
Used to adjust the anti-freeze protection of the production circuit. If the external
temperature drops below 5°C, the circulation of the production circuit pumps is
activated. If the temperature drops below 20°C in any part of the production circuit,
the heat pump starts up.
Danger:
The setting of the minimum production temperature is a very important
parameter in the start-up of the equipment. A bad configuration of this value can lead to
serious equipment damage due to freezing. The minimum production temperature must
be at least 5ºC higher than the freezing temperature of the fluid used. If you are not sure
of the freezing temperature of the fluid used, check it with a refractometer.
Compressor delay
1.
Used to adjust the duration of the compressor switched on delay.
Note:
The compressor switched on may experience extra delays due to automatic pre-start
checks.
Trial period
2.
Used to enable the trial period. If it is enabled, the heat pump is locked after the
established time.
3.
Used to adjust the duration of the trial period.
Note:
The trial period must be disabled to unlock the heat pump.
2.14.
Probe configuration
XXXXXX
1.
Display the type of probe installed in each analogue input and their current value.
2.
Used to enter a correction of the probe readings.
Note:
There are screens for all temperature and hydraulic pressure probes and for the
external temperature probe.
Production protection
MinimumT:
4.0ºC
MinimumP:
0.5bar
Anti frost:
Compressor delay
Delay:
0 min
Trial period
Enable:
Days:
30
Installer menu
2/7
a.Change language
b.Configuration
c.Information
Configuration
7/7
e.Remote control
f.Protections
g.Probe conf.
XXXXXX
Probe type:
NTC
Value:
4.1ºC
Correction:
0.0ºC