background image

 

 

 9

The unit may only be operated with a full tank.

The unit must always be disconnected from the 

electrical power source before the front hatch is dis-

mantled. Once the unit has been disconnected from 

the mains, wait until the fan has come to a standstill 

before opening the hatch.

Do not drill any holes in the unit.

Electrical Installation

The connection to the mains must be performed by a 

certified electrician. (See the enclosed electrical diagram).

The cable connecting the unit to the Design control panel 

must be a 4-conductor, 0.25-mm cable with a maximum 

length of 50 m.

System Inspection and Fine-Tuning

To ensure optimal operation of the system, fine-tune it first 

using professional air-measuring equipment.

Check the following points, while keeping in mind that the 

system can be put into operation before the fine-tuning.

1. Check that the system has been mounted correctly and 

that all ducting has been insulated in accordance with the 

instructions.

2. Check that the various hatches can be opened so that it 

is possible to service and maintain the unit.

3. Check that the filters are clean (they can be dirty after   

installation), and replace if necessary before fine-tuning.

4. Check that the condensation drainage is mounted cor-

rectly with a water trap and that this is protected against 

frost.

5. Pour 1 l of water into the condensation tray and check 

that it flows away without impediment via the conden- 

sation drainage hose. 

Default setting if the system is started up prior to  

fine-tuning:
• Adjust all supply air valves so that the valve  

which is closest to the unit is open at 3 turns from the 

closed position, while the one furthest away is open at 8 

turns from the closed position.

• Then open the valves in between at 4 to 7 turns depending 

on how close they are to the unit.

Optimal Fine-Tuning of the System

Use air-measuring equipment. Check that all 5 items in the 

section above have been carried out before performing the 

fine-tuning. Then put the system into operation.

Set up the system for basic ventilation, i.e. speed 2. To 

reduce energy consumption as much as possible, first 

adjust the overall atmospheric volume to the desired level 

by changing the speed settings in the Service Menu.

Then fine-tune the supply air and extract air valves with the 

air-measuring equipment. Remember to lock the valves 

when performing the fine-tuning and to turn the conducting 

plate on the supply air valves so that air blows in the right

direction. 

Finally, recheck and fine-tune the overall atmospheric vol-

ume by adjusting the speeds for Step 2 in the Service Menu. 

Then adjust Step 1 and Step 3 to an appropriate interval 

in relation to Step 2. 

Requirements to the Hot Water Circuit

The following materials can be used for the hot water 

installation:
• Copper

• Stainless stain

• Brass

• Synthetic materials
This naturally depends on the materials that have already 

been used in the water circuit (of the dwelling). Incorrect 

material combinations may result in corrosion damage.

This requires particular attention when  

galvanised components and  

components containing aluminium are used.

Initial Operation of the Water Circuit

• Fill the tank via the connector spigot and then air it out by 

leaving one of the uppermost hot water spigots open until 

no more air comes out.

• Recheck the entire water circuit for leaks.

• Connect the unit to the mains.
Inspect all connections of the water circuit for leaks after 

start-up.

Cooling Circuit

The unit is delivered in running order No work needs to be 

done on the cooling circuit. The control unit will automati-

cally assume control of all functions and start up the 

compressor, fan, etc. in order to maintain the set water 

temperature.

Содержание COMBI 185 BP

Страница 1: ...COMBI 185 BP INSTALLATION INSTRUCTIONS...

Страница 2: ...ater Sensor Anode 8 Electrical Installation 9 System Inspection and Fine Tuning 9 Optimal Fine Tuning of the System 9 Requirements to the Hot Water Circuit 9 Initial Operation of the Water Circuit 9 C...

Страница 3: ...erve all applicable laws and regulations The water used must be potable grade A reduction valve should be installed if the water pressure is high All connections for potable water must be certified No...

Страница 4: ...ed and as soon as the sensors detect a temperature drop in the tank The com pressor runs until the entire tank has once again reached the set temperature The Combi 185 will normally be able to satisfy...

Страница 5: ...relation to the existing water pressure and pressure loss The aspects of the installation that have to do with water must comply with the local HWS regulations The water pipes can either be made hard...

Страница 6: ...various connectors Fresh Air FRONT Discharge air Supply air Extract air Connecting Supply Air The ducting system leading from the unit to air injected in living quarters Connecting Extract Air The du...

Страница 7: ...tial of the units efficiency it is necessary to insulate the ducts properly Genvex recommends as follows Supply Air and Extract Air Ducts To minimise heat loss from the ducting system in cold lofts in...

Страница 8: ...ank is fitted with a 0 8 m2 heating coil The heat exchanger is enamelled externally The connection is 3 4 RG A sensor controlling external connections such as solar cells an oil burner or a wood burni...

Страница 9: ...7 turns depending on how close they are to the unit Optimal Fine Tuning of the System Use air measuring equipment Check that all 5 items in the section above have been carried out before performing t...

Страница 10: ...tional operational connection can be used if the function of the unit is to be supported by a wood burner or a solar collector installation Sensor T9 see the diagram on the next page measures the temp...

Страница 11: ...rne T5 T6 T8 T9 L8 Eksternt stop L9 Ikke i brug L10 Modulerende For Eftervarme L11 0 10V Motorventil Eftervarme 0 10V Ekstern bypass L16 Modbus L17 0 10V Udsugningsventilator 0 10V Indbl sningsventila...

Страница 12: ...air Sensor supply air External stop EC fan Extract air Blue Yellow EC fan Supply air Blue Yellow Control signal Motorvalve Reheating EC fan Extract air Power supply Motorvalve Reheating External Bypas...

Страница 13: ...2 Vv Varmespiral Kv T8 T7 T9 Solfanger T3 T4 T6 Betjeningspanel T5 T rrefilter Fordamper k leflade Indbl sning MA6 udligningsventil MA5 udligningsventil H jtryks pressostat Bypass T1 T2D T2S Compresso...

Страница 14: ...make sure that the maximum temperature of the do mestic hot water does not exceed 65 C and that the pres sure in the accessory heat exchanger does not exceed 3 bar Comply with all applicable local rul...

Страница 15: ...OPT 312 12 1 040384 Kompressorsamling 13 1 061014 Kompressor Large 13 1 061000 Kompressor small 14 1 045776 Anode Pos Qty Item number Description 1 1 069173 Bypass motor 2 1 045721 Heating element 3 1...

Страница 16: ...16 DECLARATION OF CONFORMITY The declaration of conformity can be found on our website www genvex com...

Страница 17: ...ilies At the same time our system is an important element when it comes to saving energy in homes and in society as a whole in fact you can recover up to 95 of the heat energy with a Genvex system All...

Отзывы: