background image

 

 

 5

INSTALLATION

Setup

Only set up the unit in 

frost-free premises.

The premises should fulfil the following prerequisites:

• Room temperature of between 8 and 35 °C for operation 

using room air

• Good insulation to adjoining premises

• Condensate drainage

• No abnormal dust load in the air

• Solid foundation (approx. 500 kg/m

2

)

To ensure problem-free operation of the unit and provide 

access for repairs and maintenance, it is recommended to 

keep 0.6 m clear in front of the unit.

On setup:

Remove the packaging material from the pallet

1.  Remove the corner protectors

2.  Remove the transport mounts on the pallet

3.  Lift the unit off the pallet and position it

4.  Align the unit by turning the adjustable support legs

KVM-Genvex A/S always recommends that you carefully 

plan where to set up your Genvex product in relation to the 

position of any living room. Since this is an engineering 

product fitted with fans and/or a heat pump, this may  

result, on rare occasions, in combination with unsuitable  

installation conditions, in unsatisfactory noise or vibration. 

As a rule, we always recommend that the system be  

installed so that it is not immediately adjacent to a bed-

room. As regards the fastening of the Genvex system to the 

building structure, we simultaneously recommend that it be 

fastened to a heavy structure like, e.g. concrete. 

Also make sure that sound or vibrations cannot be trans-

mitted through materials that are in contact with the tech-

nical system. If there is a risk of transmission of sound and 

vibrations, we recommend the additional installation 

of anti-vibration materials and the soundproofing of the 

setup room.

 

Connecting to a Water Main

During installation, to ensure that there is sufficient 

pressure and water where the water is drawn, take into 

consideration the pipe dimensions in relation to the existing 

water pressure and pressure loss.

The aspects of the installation that have to do with water 

must comply with the local HWS regulations. The water 

pipes can either be made hard or flexible. However, they 

must be approved for drinking water. Take into considera-

tion the corrosive properties of the pipes to avoid damage.

As with all pressurised containers, the tank of the unit must 

be fitted with an approved safety valve and an approved 

check valve on the supply side (always check the 

local requirements).

The inflow of fresh cold water and the outflow of hot water 

take place underneath the tank (3/4” RG connection). The 

maximum operating pressure is 10 bar, and the maximum 

operating temperature is 65 °C.

If necessary, the supply pipe must be fitted with a pressure 

reduction valve and possibly with a filter.

When fitting the piping in the dwelling, 
avoid contaminating the pipes. If required, flush 
the pipes with clean water before connecting the 
unit.

When fitting pipes, take care not to 
twist the pipe connections. Use a pipe wrench to 
apply counter pressure.

If recirculation is not used, make sure that the 
recirculation pipe connection is fastened securely.

Connecting to Condensate Drain

Quite a bit of condensate will form due to the cooling of the 

air that passes through the heat exchanger. The condensate 

drain is fitted with a hose which guides the water to a 

proper hose. 

Depending on air humidity, the flow can reach 0.5 l/h.

It is a requirement to fit the drain with a sealed water trap 

with a minimum water head of 100 mm in order to allow the 

water to drain from the unit unhindered.

If the unit is not fitted with such a water trap, the water will 

not be able to drain from the tray due to negative pressure, 

which can result in water damage. 

It is also possible for the unit to suck in air via the drain and 

since the drain contains ammonia vapours, this will damage 

the cooling system before long. 

Failure to fit the water trap properly will void the warranty.

Содержание COMBI 185 BP

Страница 1: ...COMBI 185 BP INSTALLATION INSTRUCTIONS...

Страница 2: ...ater Sensor Anode 8 Electrical Installation 9 System Inspection and Fine Tuning 9 Optimal Fine Tuning of the System 9 Requirements to the Hot Water Circuit 9 Initial Operation of the Water Circuit 9 C...

Страница 3: ...erve all applicable laws and regulations The water used must be potable grade A reduction valve should be installed if the water pressure is high All connections for potable water must be certified No...

Страница 4: ...ed and as soon as the sensors detect a temperature drop in the tank The com pressor runs until the entire tank has once again reached the set temperature The Combi 185 will normally be able to satisfy...

Страница 5: ...relation to the existing water pressure and pressure loss The aspects of the installation that have to do with water must comply with the local HWS regulations The water pipes can either be made hard...

Страница 6: ...various connectors Fresh Air FRONT Discharge air Supply air Extract air Connecting Supply Air The ducting system leading from the unit to air injected in living quarters Connecting Extract Air The du...

Страница 7: ...tial of the units efficiency it is necessary to insulate the ducts properly Genvex recommends as follows Supply Air and Extract Air Ducts To minimise heat loss from the ducting system in cold lofts in...

Страница 8: ...ank is fitted with a 0 8 m2 heating coil The heat exchanger is enamelled externally The connection is 3 4 RG A sensor controlling external connections such as solar cells an oil burner or a wood burni...

Страница 9: ...7 turns depending on how close they are to the unit Optimal Fine Tuning of the System Use air measuring equipment Check that all 5 items in the section above have been carried out before performing t...

Страница 10: ...tional operational connection can be used if the function of the unit is to be supported by a wood burner or a solar collector installation Sensor T9 see the diagram on the next page measures the temp...

Страница 11: ...rne T5 T6 T8 T9 L8 Eksternt stop L9 Ikke i brug L10 Modulerende For Eftervarme L11 0 10V Motorventil Eftervarme 0 10V Ekstern bypass L16 Modbus L17 0 10V Udsugningsventilator 0 10V Indbl sningsventila...

Страница 12: ...air Sensor supply air External stop EC fan Extract air Blue Yellow EC fan Supply air Blue Yellow Control signal Motorvalve Reheating EC fan Extract air Power supply Motorvalve Reheating External Bypas...

Страница 13: ...2 Vv Varmespiral Kv T8 T7 T9 Solfanger T3 T4 T6 Betjeningspanel T5 T rrefilter Fordamper k leflade Indbl sning MA6 udligningsventil MA5 udligningsventil H jtryks pressostat Bypass T1 T2D T2S Compresso...

Страница 14: ...make sure that the maximum temperature of the do mestic hot water does not exceed 65 C and that the pres sure in the accessory heat exchanger does not exceed 3 bar Comply with all applicable local rul...

Страница 15: ...OPT 312 12 1 040384 Kompressorsamling 13 1 061014 Kompressor Large 13 1 061000 Kompressor small 14 1 045776 Anode Pos Qty Item number Description 1 1 069173 Bypass motor 2 1 045721 Heating element 3 1...

Страница 16: ...16 DECLARATION OF CONFORMITY The declaration of conformity can be found on our website www genvex com...

Страница 17: ...ilies At the same time our system is an important element when it comes to saving energy in homes and in society as a whole in fact you can recover up to 95 of the heat energy with a Genvex system All...

Отзывы: