Figure 7:
Pin assignment of the analog input sockets
Configuration of the analog input sockets of the SiteManager II/v3 Rev. B (from SN: SMG05-
00411)
Every of the 8 analog input sockets provide the readout of the analog measurement values from
0-10V
(delivery state),
0-20mA
or rather
4-20mA
.
It is required to get the jumpers of the relative analog input socket of the main board into the accordant
position.
Please do the following, if you want to change the delivery state:
ATTENTION!!! This should be done by qualified personnel only!!!
Pull off the power supply of the SiteManager II/v3
Disconnect all cables from the SiteManager II/v3
Dismount the device
Screw off the 4 lateral screws and take-off the housing cover
Get the jumpers in their desired position (see fig. 8+9)
Delivery state (analog inputs 0-10V)
Both jumpers of the analog inputs 1-8 (channel 1-8) are set at
PIN 1+2
(see fig. 8).
In this positions of the jumpers, the following sensors are permitted for the connection at the analog
inputs and should be selected as „sensor types“ into the SiteManager II/v3 configuration only:
Custom 0-10V
SM_II_T
SM_II_T_H
SM_II_T_Plus
SM_II_VMC
SM_II_CMC