Copyright of the European Union is effective (Copyright EU) (c) 2016 GENEREX GmbH, Hamburg, Germany, All rights reserved
TEL +49(40)22692910 - EMAIL [email protected] - WEB www.generex.de (This and all other product datasheets are available for download.)
23
Figure 31:
SiteManager II/v3 gChart
4.4
Event configuration
The Event/Alarm configuration is based on a combination of events and actions (resp. Jobs). At the
SiteManager II/v3 there are various events defined, e.g. events concerning the attached devices like
“Alarm Analog Input 1”, “Alarm Digital Input 1” etc. and also events concerning a connected UPS like
“Powerfail”, “UPS Battery bad”, “Battery low” etc.
The SiteManager II/v3 allows you to release one or more actions on each event. An action can be e.g.
to write a logfile entry in the alarm logfile (as default all events do perform an logfile event), to send an
eMail or to perform an RCCMD-Command (e.g. shutdown signals to several RCCMD Clients).
To configure events and
actions open the menu “Events / Alarms”. The menu “Event
Configuration” shows you an overview about the events and the number of configured actions.
Figure 32:
HTTP - Event Configuration with tool tip
Choose the event you wish to configure to enter the event editor.