background image

are  corrosive  or  abrasive  or  detergents  containing 
chlorine or ammonia. 

 

SERVICE 

The  Air  Cleaner  when  operating  normally  will  have 

the fan running and the performance indicator light 

ON

. If 

this is not the case the see the Troubleshooting Guide for 
probable causes and remedies.  

Testing For High Voltage At Power Board 

For the following test you will need to have the hinged 

cover open with the 

collecting cell out of the unit

.  

1.  Remove the hinged cover and the cover panel to the 

power box. Push a screwdriver into the slot to defeat 
the interlock switch and turn the Air Cleaner 

ON

.  

2.  With a long shafted screwdriver, with a plastic handle, 

short  between  the  grounded  side  of  the  power  box 
and the HV1 terminal of the power board. 

3.  If  you draw  a good spark, there is high voltage from 

the power board.  
 

Measuring High Voltage At Power Board

 

A  high  voltage  meter  capable  of  measuring  up  to 

10,000 VDC is required to test the voltage. 
1.  The Air Cleaner should be 

ON

 with the cell installed 

and  the  cell  access  door  closed.  The  Air  Cleaner 
should  be  on  at  least  5  minutes  to  allow  voltage  to 
stabilize. 

2.  Remove  the  hinged  cover  and  the  cover  panel  from 

power box. 

3.  Connect  the  ground  of  the  high  voltage  meter  to 

ground stud in the power box. 

4.  Turn  the  Air  Cleaner 

ON

,  and  defeat  the  interlock 

switch. 

5.  Check terminals HV1 and HV2 on the power board to 

determine if voltage is present. See Fig. 5 for values.. 

5.  If no voltage is present, remove the cell from the Air 

Cleaner. 
a.  Check the voltage at HV1 and HV2 again. 
b.  If voltage is present,  the problem is  with the cell 

or the wiring to the copper contacts. 

c.  Check  the  condition  of  the  copper  contacts  and 

wiring. 

d.  If the contacts are not bent and the wiring is OK,  

the  problem  is  with  the  cell.  See  the 
Troubleshooting Guide for more information. 

e.  If there is no voltage with the cell removed, check 

the power  board, system switch and  transformer 
to make sure that they are functioning correctly. 

6.  If  there  is  voltage  present,  but  the  performance  light 

does not come on, replace the light. 

7.  The  high  voltage  can  be  adjusted  with  the 

potentiometer on the power board if required. 

 
Replacing A Performance Light 

Before  replacing  the  performance  light,  turn 

OFF

 

power to the Air Cleaner at the source.  
1.  Remove the cover and the power box cover panel. 
2.  Disconnect the performance light wiring connected to 

the  neon  lamp  terminals  (P5  and  P6)  on  the  power 
board.  Carefully  cut  the  wire  ties  from  the  wire 
bundle. 

3.  Push the light out through front of power box. 
4.  Push the new light into the power box. 
5.  Connect the wiring to the neon lamp terminals on the 

power board, P5 and P6. Route the wires away from 
the high voltage section of the power board. 

6.  Replace cover panel and close the cover. 
7.  Return power to Air Cleaner. Test light. 

 
Replacing A Power Board 

Before replacing the power board, turn 

OFF

 power to 

the Air Cleaner at the source. 
1.  Remove the cover and the power box cover

 

panel. 

2.  Disconnect the wiring from the neon lamp, HV1, HV2 

and 24 V terminals. Make note of position of wires. 

3.  Remove the hex nuts from the power board. 
4.  Remove the power board from the studs. 
5.  Place the new board onto studs with the 24 volt input 

close to the transformer. 

 

Fig.  4 

  DAX  Detergent  is   

available  in  35  ounce  (1  litre) 
spray  bottles  or  1  gallon  (4.54  L) 
and  4.8  gallons  (22  L)  containers 
from your installer or dealer.  

 

WARNING  

Electronic  Air  Cleaners  use  high  voltage  (low 
amperage).  Only  trained  personnel  should  perform 
service. 

USE  CAUTION!

  Electric  shock  can  cause 

injury or death.  

CAUTION  

For  most  troubleshooting  the  cell  should  be 
removed from the  Air Cleaner.

 A short in the cell will 

cause  the  power  board  to  shutdown  and  the 
performance  light  will  stay  off.  Unless  otherwise 
directed remove the cell from the unit when testing.  

WARNING  

When performing LIVE tests in the power box 

NEVER

 

touch  any  parts  other  then  what  are  mentioned  in  the 
tests.  Components  carry  dangerous  voltages  and 
extreme care must be taken. 

Содержание SSCB-7 SERIES

Страница 1: ...Operation And Maintenance Manual SSCB 7 SERIES SEMI FLUSH CEILING MOUNTED ELECTRONIC AIR CLEANER IMPORTANT PLEASE READ MANUAL BEFORE INSTALLING OPERATING CLEANING OR SERVICING UNIT...

Страница 2: ...ple of Electrostatic Precipitation Millions of airborne pollutants are drawn through the intake grill on the bottom of the Air Cleaner and first pass through a Prefilter which removes all large visibl...

Страница 3: ...e wiring compartment INSTALLATION 1 Read instructions carefully Failure to do so may result in product damage or injury 2 Make sure the sizing is correct for your application 3 Installation should be...

Страница 4: ...ing is an average wash cycle Stores Offices Computer Conference Rooms 4 Weeks Cafeterias Restaurants Lounges 3 4 Weeks Bars Bingo halls 1 3 Weeks The unit should be checked on a regular basis to deter...

Страница 5: ...tch and transformer to make sure that they are functioning correctly 6 If there is voltage present but the performance light does not come on replace the light 7 The high voltage can be adjusted with...

Страница 6: ...lead with the two white leads from the terminal block and connect with the wire nut you removed earlier 10 Replace power box cover panel and close cover 11 Turn ON the power to the Air Cleaner and te...

Страница 7: ...until a replacement is received 4 Place one end of the loop over the finger at the bottom of the cell 5 Using needle nose pliers grip the other end of wire near the bottom of the top loop Pull the wi...

Страница 8: ...Fig 6 Electrical Schematic With Wired Remote 120 Volt Fig 5 Electrical Schematic 120 Volt 8...

Страница 9: ...mance indicator light is ON Defective power switch Check power switch for continuity with ohmmeter Replace if defective Defective speed selector switch Check switch for continuity with ohmmeter Replac...

Страница 10: ...ncl Grill Gray EACCM7 06G 7 Collecting Cell EACCM7 07 8 Cell Handle EAC14 16 9 Ionizing Wire EAC20 19 10 Safety Interlock Switch EACCM13 10 11 Red Indicator Light EACCM13 11 Description Part Number 12...

Страница 11: ...in 71 0 cm Height 15 in 38 1 cm Weight 70 0 lbs 32 0 kg Input Voltage 120 V 60 Hz Power Consumption maximum 150 Watts Air Flow Hi 712 CFM 1210 m3 hr Medium 575 CFM 977 m3 hr Low 440 CFM 748 m3 hr Moto...

Страница 12: ...General Filters Inc THERE ARE NOT EXPRESS WARRANTIES COVERING THIS ELECTRONIC AIR CLEANER OTHER THAN AS SET FORTH ABOVE THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE A...

Отзывы: