the unit so that the flange is flush with the underside 
of the ceiling. 

Leave enough room around the Air Cleaner for 
removal of collecting cell and prefilter. 

7.  Replace  the  cell,  prefilter  and  cover.  Hook  up  the 

safety chain to the cover. 

Do not hang the unit with chain only. This will not  

give  the  unit  the  necessary  stability  when  removing 
the cells or servicing the unit. 
 
Wiring 

All  wiring  must  comply  with  applicable  codes  and 

standards.  See  unit  rating  label  for  correct  voltage  and 
amperage. 
1.  Two knockouts are provided, one on top and one on 

the  side  of  the  unit,  adjacent  to  the  wiring 
compartment. For convenience, a wall switch may be 
installed  near  the  Air  Cleaner,  in  series  with  the 
power source, to turn the unit on and off. 

2.  Remove  the  cover  of  the  wiring  compartment  to 

locate  the  input  leads  and  ground  stud.  The  Air 
Cleaner  must  be  grounded  for  proper  operation  and 
safety. 

3.  Once the unit is mounted and wired, the cover can be 

replaced on the hinge and the chain replaced on the 
"S"  hooks.  Close  the  cover  by  sliding  the  levers 
toward  the  center  and  pushing  the  cover  up  into 
place. Release levers to lock the cover into place. 

 

For  information  on  wiring  the  remote  switch 

control see page 7. 

 

OPERATION & MAINTENANCE 

Operation Check

 

1.  With  the  cell  and  prefilter  in  place  and  the  cover 

closed, turn the system switch 

ON

2.  Adjust the fan speed with the slide switch. Insure the 

unit functions on all speeds. 

3.  The performance  light should be 

ON

, which indicates 

the power board is functioning properly. 

4.  If  the  unit  is  not  functioning  properly  see  the 

"Troubleshooting Guide"  
When the Air Cleaner is new it may arc or periodically 

make "snapping sounds". A slight odor of ozone may be 
noticeable. The arcing and odor are due to rough edges 
and  burrs  on  the  cell.  These  symptoms  will  disappear 
during the first few weeks of normal operation. The ozone 
levels are well below government standards for indoor air 
concentration. 

Maintenance Schedule 

The collecting cell and prefilter must be cleaned on a 

regular basis for the unit to function at its peak efficiency. 

The frequency of cleaning will vary from one environment 
to another. The following is an average wash cycle: 

Stores, Offices, Computer & Conference Rooms = 

Weeks

 

Cafeterias, Restaurants, Lounges = 

3-4 Weeks

 

Bars, Bingo halls = 

1-3 Weeks 

 

The unit should be checked on a regular basis to 

determine the frequency of cleaning required in each 
location and a cleaning schedule established. 

 

Cleaning 

1.  Turn  off  the  system  switch  and  wait  15  seconds  for 

high voltage to dissipate. 

2.  Open  the  cover  and  cell  access  door  and  remove 

collecting  cell  and  prefilter. 

Cell  plates  are  sharp. 

Handle with care.

 

3.  Place  cell  in  tub  and  spray  completely  with 

DAX 

Detergent

, allowing detergent to run down both sides 

of  plates  and  ionizing  wires.  Let  sit  for  5  minutes. 
Rinse  cell  well  with  hot  water  (140ºF  /  60ºC 
maximum). Repeat washing process if necessary. 

4.  If dirt or nicotine remains on plates, let cell soak in hot 

soapy  water  for  30  minutes. 

Never  use  any 

instrument to clean the cell, as this may damage 
the ionizing wires or bend cell plates. 

5.  Spray prefilter with 

DAX Detergent

 and rinse well. 

6.  To  dry  cell,  tilt  on  45º  angle  against  wall  with  the 

arrow  pointing  sideways.  Allow  to  dry  completely  for 
10-24 hours. Place in sunlight for faster drying time. 

7.  When the cell and prefilter are dry,  place  them back 

into the unit. The arrow on the cell points up. The red 
fiberboard on the cell should line up with the contacts 
in the cabinet. Close door and cover. If the cell  arcs 
when  the  switch  is  turned  on  or  if  the  performance 
light does not come on, then the cell may be still wet. 
Allow more time for drying. 

The use of 

DAX  Detergent

 is strongly recommended 

for cleaning as it is a heavy-duty solution used expressly

 

for  removal  of  accumulated  pollutants  on  cell  plates.  If 
used  as  directed, 

DAX

  will  not  harm  aluminum  or  steel. 

Any  problem  arising  out  of  the  use  of  another  cleaning 
agent  will  void  the  warranty.  Do  not  use  detergents  that 

WARNING 

Electrical shock can cause injury or death. Be certain 
main line disconnect switch is off before wiring.  

CAUTION 

Make  sure  Air  Cleaner  switch  is 

OFF 

before 

performing  any  maintenance  or  removing  any 
components.  

CAUTION  

Damage  to  cell  may  occur  if  improperly  handled  or 
washed. 

Do  not  wash  cell  in  a  dishwasher.

 Never 

use any object to clean between the cell plates, as this 
may cause damage to plates or ionizing wires. Never 
place cell in oven to dry. The edges of the cell may be 
sharp - handle with care.  

Содержание SSCB-7 SERIES

Страница 1: ...Operation And Maintenance Manual SSCB 7 SERIES SEMI FLUSH CEILING MOUNTED ELECTRONIC AIR CLEANER IMPORTANT PLEASE READ MANUAL BEFORE INSTALLING OPERATING CLEANING OR SERVICING UNIT...

Страница 2: ...ple of Electrostatic Precipitation Millions of airborne pollutants are drawn through the intake grill on the bottom of the Air Cleaner and first pass through a Prefilter which removes all large visibl...

Страница 3: ...e wiring compartment INSTALLATION 1 Read instructions carefully Failure to do so may result in product damage or injury 2 Make sure the sizing is correct for your application 3 Installation should be...

Страница 4: ...ing is an average wash cycle Stores Offices Computer Conference Rooms 4 Weeks Cafeterias Restaurants Lounges 3 4 Weeks Bars Bingo halls 1 3 Weeks The unit should be checked on a regular basis to deter...

Страница 5: ...tch and transformer to make sure that they are functioning correctly 6 If there is voltage present but the performance light does not come on replace the light 7 The high voltage can be adjusted with...

Страница 6: ...lead with the two white leads from the terminal block and connect with the wire nut you removed earlier 10 Replace power box cover panel and close cover 11 Turn ON the power to the Air Cleaner and te...

Страница 7: ...until a replacement is received 4 Place one end of the loop over the finger at the bottom of the cell 5 Using needle nose pliers grip the other end of wire near the bottom of the top loop Pull the wi...

Страница 8: ...Fig 6 Electrical Schematic With Wired Remote 120 Volt Fig 5 Electrical Schematic 120 Volt 8...

Страница 9: ...mance indicator light is ON Defective power switch Check power switch for continuity with ohmmeter Replace if defective Defective speed selector switch Check switch for continuity with ohmmeter Replac...

Страница 10: ...ncl Grill Gray EACCM7 06G 7 Collecting Cell EACCM7 07 8 Cell Handle EAC14 16 9 Ionizing Wire EAC20 19 10 Safety Interlock Switch EACCM13 10 11 Red Indicator Light EACCM13 11 Description Part Number 12...

Страница 11: ...in 71 0 cm Height 15 in 38 1 cm Weight 70 0 lbs 32 0 kg Input Voltage 120 V 60 Hz Power Consumption maximum 150 Watts Air Flow Hi 712 CFM 1210 m3 hr Medium 575 CFM 977 m3 hr Low 440 CFM 748 m3 hr Moto...

Страница 12: ...General Filters Inc THERE ARE NOT EXPRESS WARRANTIES COVERING THIS ELECTRONIC AIR CLEANER OTHER THAN AS SET FORTH ABOVE THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE A...